Control screens – Raypak LONMARK Y-200 User Manual

Page 13

background image

13

Control Screens

To access programming mode: Press and hold the

"MODE" button for 4 seconds. When in Program

mode, cursor is blinking on first settable parameter.

UP/DOWN arrows change parameter. LEFT/RIGHT

arrows move to next selectable parameter.

Table E: Control Screens

NOTE: Once programming is finished, go to

Screen 28 to program the USER DEFAULT

SET_UP. Then open the front panel and press

the SW3 reset button on the motherboard to save

the new programming.

T

L

U

A

F

E

D

Y

R

O

T

C

A

F

N

O

I

T

P

I

R

C

S

E

D

N

E

E

R

C

S

Initial Screen

01

Displays the product identification and version of software.

Calendar, Time, Initial

Setpoint

02

The present month, day, year and time in a 24-hour clock

format; setpoint temperature.

°F or °C

02

Temperature can be displayed in degrees Fahrenheit or

F

°

=

e

u

l

a

v

tl

u

a

f

e

D

s

u

i

c

l

e

C

Setpoint

02

40 to 220 °F (4.4 to 104.4 °C); the system output

temperature desired when the outdoor temperature is 70 °F

(21.1°C); or in domestic hot water applications, the desired

water temperature.

Default = 140 °F

(60°C)

Control Band

03

1 to 10°F; the temperature above and below the Target

Temperature at which the boiler turns off and on. NOTE: The

Control Band is disabled in PID operation. If the Control

Band is adjusted during PID operation, it disables the PID

function.

Default = 3° F. No

value when in PID

Offset

04

Degrees of offset added to or subtracted from the initial set

point at the date and time selected.

Default = OFF

Setting Holiday

05

Data from screen 04 is combined with these screen settings.

Default = 00-00-RH

Reset Ratio

06

None (for Domestic Hot Water Application ONLY) or 0.01:1 to

8:1; determines how much the internally-calculated Target

Temperature will change for a given outdoor temperature

change.

Default value =

200°F@10°F

(93.3°[email protected]°C)

System Status

07

Shows the status of the system.

Water Temperature

Limits

08

Maximum "USER" water temperatures 235°F (112.7°C) and

Minimum water temperatures 40°F (4.4°C)

Display

Only.

Max default value=

180°F / 82.2°C

Min default value=

105°F / 40.5 °C

Changes: Screen 23.

Outdoor Cut-off

Temperature

09

32 to 200°F (0 to 93.3°C), a warm-weather shutdown feature.

When the outdoor temperature exceeds this setting, the

boiler will not fire unless placed in manual override mode.

Default value = 75 °F

(23.8°C)

Outdoor Cut-off

Deadband

10

-01 to -10°F; the number of degrees below the Outdoor Cut-

off Temperature which causes the Outdoor Cut-off

Temperature to reset.

Default value = -3°F

System/Network Monitor

11

Displays the Pump, Boiler, Stage and Auxiliary contact

status. If flashing, contacts are closed (ON).

This screen is

DISPLAY only.

Outdoor Water TAR

12

Displays the current Outdoor Air, System Water and Target

Temperature in degrees °F or °C.

Default = °F

AUX Delay

13

000 to 600 seconds; determines when the pump shuts off

after entering Outdoor Cut-off mode.

Default = 180 seconds.

Boiler/Stage On Delay

14

0 to 600 seconds; sets the time interval between sequential

boiler start-ups. 0 to 600 seconds;

sets time interval between stages turning on.

Default = 10 seconds.

Disabled in PID.