Control Band:

3

0

D

N

A

B

L

O

R

T

N

O

C

X

X

.

X

°

F

*C Band is a range of temperature above and below

the target temperature.

Range: 1°F to 10°F (.5°C to 5.5°C)

Default value is 3°F

Screen number

Fahrenheit or Celsius

NOTE: The above settings are recommended at

initial installation. For maximum performance and

system efficiency, these settings should be modified

as required to meet such parameters as system

capacity, location and usage.

NOTE: The Control Band is disabled when the unit

is operating in PID mode.

Control Band (Proportional Only)

The Control Band sets the maximum temperature above and below the Target Temperature (which is determined

by the embedded microcontroller) between which the system temperature may deviate.

This provides a control dead-band that prevents the boiler from short-cycling in proportional mode.

Control Band is a range of temperature above and

below the target temperature.

NOTE: PID mode will be disabled if you adjust the

control band.