Manual Override

Internal switches have been provided on each of the stage modules that can be used to manually override the

microcontroller. See switch SW1 on each stage board, page 15.

Boiler/Stage Off Delay

15

0 to 600 seconds; sets the time interval between sequential

boiler start-ups. 0 to 600 seconds;

sets time interval between stages turning off.

Default = 10 seconds.

Disabled in PID.

Standard or PID

16

Selects either Standard or PID operation.

If PID

is selected then PID & Interval is programmable using screen

D

I

P

=

tl

u

a

f

e

D

.

4

3

Boiler Inlet/ Outlet Delta

(Optional)

17

Displays the boiler inlet and outlet temperature in °F or °C

and the difference (delta) between them. (Requires 4-

sensor installation, option Y-306.)

INLET / OUTLET =

Delta T

Auto Lead-Last

18

The lead change time in hours, the lead and last boiler

numbers and the mode (either Auto or Manual).

Manual: Default = 100

hours.

Password

19

Used to enter a password. This allows

access to screens 20 through 34.

Default = AAA To

change: screen 22.

Unit Set-up / Network

20

Sets up the pump, boiler and stage configuration for the

System Monitor (Screen 11).

Preset =

2 boilers / 4 stages.

Default =

PBSSSBSSSAAA

Note: See Table J.

System Test

21

When ACTIVE, initiates auto system test and displays all

e

v

it

c

A

t

o

N

=

tl

u

a

f

e

D

.

s

n

e

e

r

c

s

Set Password

22

Changes the current user password.

Default = AAA

Water Temperature

Limits

23

Sets Maximum and Minimum water tempterature limits

allowed by the user in the Water Temperature Screen

Min. Default = 105°F

(40.5°C), Max. Default

= 210°F (98.8°C)

Master/Slave Unit

24

Displays the number of sensors utilized, relays (stages or

boilers) and Aux contacts.

Default = Master

Slaves Conneted

25

Selects the number of slave units connected, if any.

Default = 00

LonWorks

26

If ON, the LonWorks network will be active.

Default = OFF

Factory Defaults

27

If YES selected, the factory defaults will be restored.

Default = NO

User Defaults

28

If YES is selected, the User Defaults can be stored or

e

n

o

N

=

tl

u

a

f

e

D

.

d

e

k

o

v

n

i

Terminal Password

29

Used to enter a password for modem operation.

Default = AAA

Alarm Call Tele

30

Modem system telephone number to be called when a fault

e

n

o

N

.

s

r

u

c

c

o

Alarm Call ID

31

Modem system ID person or place to be called when a fault

e

n

o

N

.

s

r

u

c

c

o

Alarm Call Retry

32

Modem sy

e

n

o

N

.

s

e

ir

t

e

r

ll

a

c

r

o

r

r

e

m

e

t

s

Alarm Call Events

33

Modem sy

e

n

o

N

.

s

n

o

it

a

c

i

d

n

i

r

o

r

r

e

m

e

t

s

PID Settings

34

Configures PID operation.

Default =

Interval = 05

KP = 06

KI = 05

KD = 01

Table F: Control Screens Continued