Electrical ( millivolt) – Raypak Versa 105B User Manual
Page 27
If pilot burner remains lit.
Jump across pressure
switch terminals
If main burner does not
fire, remove jumper
Check for adequate water
flow from filter
Replace pressure switch
Jump across thermostat
If main burner fires,
remove jumper
If main burner does
NOT fire...
Jump across each high
limit and remove jumper
Replace thermostat
Replace high limit that
caused heater to fire
Jump across both "TH"
wires on gas valves
Check gas supply, gas
line size, gas pressure.
Also check for insects
or debris in pilot output.
If pilot burner
does not light
Light pilot
CAUTION: For qualified service personnel only.
1.
Filter must be on with adequate water flow through heater.
2.
Gas valve must be "ON" position. Thermostat set higher
than pool water temperature.
3.
Jumpers are for temporary check only. If left in place,
they could cause the heater to burn up.
If pilot burner goes out
when main burner lights
or when gas valve knob
is released
If burner does not remain
lit, attach millivolt meter
and read pilot output.
If below 500mV, check
gas pressure. Also check
for insects or debris in
the pilot burner
If main burner fires,
remove jumper
Replace
gas
valve
If main burner does not
fire, remove jumper
Remove both "TH"
wires from gas valve.
Relight pilot
If pilot burner stays on
Problem is a wire or
component short to
cabinet or low gas
pressure
If above 500mV,
replace gas valve
Clean filter
If main burner fires,
remove jumper
Leaking at well.
Overacid..................................
Replace well and maintain water chemistry
properly.
Leaking at heat exchanger.
Overacid..................................
Replace heat exchanger and maintain
chemistry properly.
Gasket brittle and leaking -
Heater running after pump
(overheated).
shuts off...................................
See pressure switch adjustment.
Refractory damage.....................
Replace refractory.
Sooted heater............................
Determine cause of sooting and correct.
RAYPAK POOL OR SPA HEATER ELECTRICAL
CHECK WITH MV GAS VALVE
If output is still low,
replace pilot generator.
Liming
Bypassing too much water............ Inspect bypass for movement, if no movement,
replace.
27
ELECTRICAL ( MILLIVOLT)