CLEARANCES

ALL HEATERS

For clearances from combustible surfaces, see

chart below.

Clearances from Combustible construction.
Indoor Installation:

Top* (Drafthood) - 30"; Vent - 6";
Back - 5"; Right Side - 6";
Left Side - 6"; Floor - 0.

Outdoor Installation:

Top* (Stackless Top) -
unobstructed; Back - 5"; Sides - 6".

* Clearance from Top of Vent Terminal

For servicing, provide at least 24" in front of the

heater for burner tray removal, and at least 18" on the left
side of the heater to inspect and delime the heat
exchanger.

10

OUTDOOR HEATERS

These heaters are design certified for outdoor

installation, when equipped with the approved top des-
ignated for outdoor use.

WARNING: The heater shall not be located in an area
where water sprinklers, or other devices, may cause
water to spray through the cabinet louvers and into the
heater. This could cause heavy internal rusting or
damage some electrical components, and this would
void the warranty.

Heaters must not be installed under an overhang of less than three (3) feet from the top of the heater. Three

(3) sides must be open in the area under the overhang. Roof water drainage must be diverted away from the heaters
installed under overhangs with the use of gutters:

The point from where the flue products exit the heater must be a minimum of four (4) feet below, four (4) feet

horizontally from or one (1) foot above any door, window or gravity inlet to a building. The top surface of the heater
shall be at least three (3) feet above any forced air inlet, or intake ducts located within ten (10) feet horizontally.

Heater with outdoor top

Fig # 9259

4

foot

Minimum

4

foot

Minimum

1

foot

Minimum

4

foot

Minimum

3

foot

Minimum

10

foot

Minimum

Forced Air Inlet