Regency P48 Zero Clearance Direct Vent Gas Fireplace

7

INSTALLATION

The HeatWave Duct Kit
and the Heat Release
Kit have different clear-
ance and framin require-
ments, check the Heat-
Wave
and Heat Release
manual for details.

Heat Release Kit

CLEARANCES

The clearances listed below are Minimum distances unless otherwise stated:

A major cause of chimney related fires is failure to maintain required clearances (air space) to combustible materials. It is of
the greatest importance that this fireplace and vent system be installed only in accordance with these instructions.

Clearance to Combustibles from:

Back

0"

(0mm)

Side

0"

(0mm)

Floor

0"

(0mm)

Minimum Clearance from Top of Front Facing:

Mantel

min. 8"

(203mm)

Ceiling

39"

(990mm) from top of front facing above louvers.

Side Wall:

6"

(152mm)

Horizontal Vent Clearances:

Top

2-1/2"

(64mm)

Side

1-1/2"

(38mm)

Bottom

1-1/2"

(38mm)

Vertical Vent Clearances:

1-1/4"

(32mm)

Alcove Clearances:

Max. Depth

36"

(914mm)

Min. Width

60"

(1524mm)

Min. Height

80"

(2032mm)

Caution Requirements

The top, back and sides of the fireplace are defined by

standoffs. The metal ends of the standoff may NOT be

recessed into combustible construction.

WARNING

Fire hazard is an extreme risk

if these clearances (air space) to combustible materials

are not adhered to. It is of greatest importance that this

fireplace and vent system be installed only in

accordance with these instructions.