Regency P48 Zero Clearance Direct Vent Gas Fireplace

16

INSTALLATION

Horizontal Venting with Three (3) 90

o

Elbows

Option V

H V + V1

H + H1

A)

2' Min.

1' Max.

3' Min.

4' Max.

B)

3' Min.

2' Max.

4' Min.

5' Max.

C)

4' Min.

3' Max.

6' Min.

6' Max.

D)

5' Min.

4' Max.

8' Min.

7' Max.

E)

6' Min.

5 Max.

10' Min. 8' Max.

F)

7' Min.

6' Max.

12' Min. 9' Max.

Vertical Venting with Two (2) 90

o

Elbows

Option V

H

V + V1

A)

1' Min.

4' Max.

2' Min.

B)

2' Min.

5' Max.

3' Min.

C)

3' Min.

6' Max.

4' Min.

D)

4' Min.

7' Max.

5' Min.

E)

5' Min.

8' Max.

6' Min.

Vertical Venting with Two (2) 90

o

Elbows

With these options, max. total
pipe length is 30 feet with min.
of 6 feet total vertical and max.
8 feet total horizontal.
Please note min. 1 foot
between 90

o

elbows is re-

quired.

Option H + H1 V
A)

2' Max. 2' Min.

B)

3' Max. 3' Min.

C)

4' Max. 4' Min.

D)

5' Max. 5' Min.

E)

6' Max. 6' Min.

With these options, max. total
pipe length is 30 feet with min.
of 6 feet total vertical and
max. 6 feet total horizontal.
Please note min. 1 foot
between 90

o

elbows is re-

quired.

One 90

o

elbow = Two 45

o

elbows.

One 90

o

elbow = Two 45

o

elbows.

One 90

o

elbow = Two 45

o

elbows.

For additional vertical vent-
ing with 2 x 90

o

elbows,

refer to page 18.

With these options,
max. total pipe length
is 30 feet with min. of
12 feet total vertical
and max. 9 feet total
horizontal.
Please note min. 1
foot between 90

o

elbows is required.