10-10

Page 18
2008-12-03

1.1.9 Configuring the humidification box drying

An occasional drying of the humidification boxes helps prevent germs and bacteria
from developing in the humidification boxes. The drying process can be time

triggered

or, interval controlled, or it can be deactivated.

Note: During operation, the drying process of the humidification boxes can lead to a
temporary humidity decrease.

Select “Box Drying” in the settings menu, then
press the key. The current settings for
the box drying function appear. The settings
available depend on whether the box drying
function is deactivated (Off, factory setting) or
whether the time controlled (Timer) or the
interval controlled (Periodic) triggering of the
drying function is selected.

Drying function deactivated (Off ---> factory
setting)

Time controlled drying (Timer)With the
parameters “time 1” to “time 4 ” you can define
up to four times of day to start a box drying
process (factory setting: no starting times
defined).

Interval controlled drying (Periodic) With the
parameter “Periodic Int” you can determine inn
which time intervals a box drying process is
performed (setting range: 0.5 ...24 .0h, factory
setting: 12.0h).