1.1.4 Setting the capacity limitation

Select “Power Limit” in the settings menu,
then press the key. In the upcoming
modification dialogue set the desired capacity
limitation in % of the maximum capacity of the
humidifier.

Factory setting:
100 %
Setting range:
30...100 %


1.1.5 Configuring the supply pipe flushing

Select “Inlet Flush” in the settings menu, then
press the key.

Used to configure the unit to flush supply lines
even if there is no demand signal. You can;
- enable / disable inlet flush
- set length of flush
- set time between flushes

DESCRIPTION OF THE SETTINGS
Inlet Flush

Enable or disable the supply pipe flushing.

Factory setting: On
Options:

On (enable)

Off

(disable)

Drain Time

Setting the flushing time in seconds.

Factory setting:
60s
Setting range:

5...600s

Periodic Int

Setting the time without demand after which
the supply pipe should be flushed.

Factory setting: 12.0 h
Setting range:

0.5 ... 24.0 h