1.1.4 Setting the capacity limitation
Select “Power Limit” in the settings menu,
then press the
modification dialogue set the desired capacity
limitation in % of the maximum capacity of the
humidifier.
Factory setting: 100 %
Setting range: 30...100 %
1.1.5 Configuring the supply pipe flushing
Select “Inlet Flush” in the settings menu, then
press the
Used to configure the unit to flush supply lines
even if there is no demand signal. You can;
- enable / disable inlet flush
- set length of flush
- set time between flushes
DESCRIPTION OF THE SETTINGS
Inlet Flush
Enable or disable the supply pipe flushing.
Factory setting: On
Options:
On (enable)
Off
(disable)
Drain Time
Setting the flushing time in seconds.
Factory setting: 60s
Setting range:
5...600s
Periodic Int
Setting the time without demand after which
the supply pipe should be flushed.
Factory setting: 12.0 h
Setting range:
0.5 ... 24.0 h