Nortec MH Series User Manual
Page 17
10-10
Page 13
2008-12-03
1.1.3 Control Settings
Select “Controls” in the settings menu, then
press the
The control settings appear. The settings
available depend on the selected signal
source and the control type. The opposite
display shows the maximum number of
settings available.
DESCRIPTION OF THE SETTINGS
SignalSource
Selecting the signal source.
Factory setting: Analog
Options:
Analog
Modbus
Hum.Control:
Selecting the control type.
Factory setting: External
Options: External (external continuous controller)
24VOn/Off (external On/Off humidistat)
Int. (P) (Internal P controller)
Int. (PI) (Internal PI controller)
Controlsign.
Selecting the control signal.
NOTE: This setting is available only if control type
“External”, “Int. (P)” or “Int. (PI)” is selected.
Factory setting: 0–10V
Options: 0–5V, 1–5V, 0–10V, 2–10V, 0–16V, 3.2–
16V, 0–20mA, 4–20mA
Hum.Setpoint:
Setting the
n
ominal humidity value inn %rh.
NOTE: This setting is available only if the internal P
or PI controller is activated.
Factory setting: 50 %rH
Setting range: 20...99 %rH
P-Band:
Setting the proportional range inn % for the internal
P/PI conntroller.
NOTE: This setting is available only if the internal P
or PI controller is activated.
Factory setting: 18 %
Setting range: 1...100 %
Integr.-Time:
Setting the integral time in minutes for the internal
PI controller.
NOTE: This setting is available only if the internal P
or PI controller is activated.
Factory setting: 18 Minutes
Setting range: 1...60 Minutes