NI 9213 Conversion Speed Control
The NI 9213 converts at two pre-defined rates, as controlled by the speed
control field.
Note
The conversion rate assumes that 18 channels are in the scan list.
NI 9213 Common Mode Error/Status
The error/status field is shown in Table 22.
NI 9213 Scan List
The scan list contains channels to convert, in order. The NI 9213 has
eighteen measurable channels:
•
0..15: Sixteen thermocouple channels (always measured in a ±78 mV
range)
•
16: One cold junction channel (always measured in a ±2.5 V range)
•
17: One auto zero channel (always measured in a ±78 mV range)
Table 21. NI 9213 Conversion Speed Control
Speed Control
Meaning
Conversion
2 (0x02)
High-Accuracy
55 ms/channel (.99 s total)
15 (0x0F)
High-Speed
740
μs/channel (13.32 ms total)
Table 22. NI 9213 Error Status Field
Bits
Field
31:8
Reserved
7
OT Error:
1= Open thermocouple was detected on the
last channel that was acquired
6
CMV Error:
1= Common mode voltage error was
detected on the last channel that was
acquired
5
GO Status: status of the gain override enable
bit
4
Reserved
3:0
Currently configured ADC data rate