— 13 —

EN61000-4-4 (EFT), level 3

EN61000-4-5 (Surge), level 3

EN61000-4-2 (CS), level 3

Shock IEC

60068-2-27

Free Fall

IEC 60068-2-32

Vibration IEC

60068-2-6

WARRANTY

5 years

EMS Type Tests

Test Description

Test

Levels

Severity
Levels

Air
discharge

+/- 8 KV

3

Contact
discharge

+/- 6 KV

3

IEC
61000-4-2

ESD

ESD
contact
indirect

+/- 6 KV

3

IEC
61000-4-3

Radiated
RFI

Housing

10 V/m, 80 MHz – 1 GHz,
AM 1 KHz 80% modulation
10 V/m, .9 GHz – 1.8 GHz,
FM 200 Hz 50% square

3

Power
supply
lines

+/- 2 KV

3

Comm.
lines

+/- 1 KV

3

IEC
61000-4-4

Burst
(Fast
Transient)

Relay

+/- 1 KV

3

Power
supply
lines

+/- 2 KV, 12

Ө, CM; +/- 1KV,

2

Ө, DM

3

IEC
61000-4-5

Surge

Relay

+/- 1 KV, 42

Ө, CM; +/- 1KV,

42

Ө, DM

3

Power
supply
lines

10 Vrms, 150 KHz – 80
MHz, AM 1 KHz 80%
modulation

3

Comm.
lines

10 Vrms, 150 KHz – 80
MHz, AM 1 KHz 80%
modulation

3

IEC
61000-4-6

Induced
(Conducted)
RFI

Relay

10 Vrms, 150 KHz – 80
MHz, AM 1 KHz 80%
modulation

3

Environmental Type Tests

Test Description

Test

Levels

IEC 60068-2-6

Vibration

10 – 500 – 10Hz, 0.5 oct./min.,
4g, X, Y, Z (3 axes)

IEC 60068-2-27

Shock

50 g, 11 ms,

̈́X, ̈́Y, ̈́Z

(6 directions)

IEC 60068-2-32

Free Fall

75 cm, 1 corner, 3 edges, 6 faces
(total 10 drops)