Chapter 7

Counters

NI 6238/6239 User Manual

7-24

ni.com

Frequency Generation

You can generate a frequency by using a counter in pulse train generation
mode or by using the frequency generator circuit.

Using the Frequency Generator

The frequency generator can output a square wave at many different
frequencies. The frequency generator is independent of the two
general-purpose 32-bit counter/timer modules on M Series devices.

Figure 7-26 shows a block diagram of the frequency generator.

Figure 7-26. Frequency Generator Block Diagram

The frequency generator generates the Frequency Output signal. The
Frequency Output signal is the Frequency Output Timebase divided by a
number you select from 1 to 16. The Frequency Output Timebase can be
either the 20 MHz Timebase divided by 2 or the 100 kHz Timebase.

The duty cycle of Frequency Output is 50% if the divider is either 1 or an
even number. For an odd divider, suppose the divider is set to D. In this
case, Frequency Output is low for (D + 1)/2 cycles and high for (D – 1)/2
cycles of the Frequency Output Timebase.

Figure 7-27 shows the output waveform of the frequency generator when
the divider is set to 5.

Figure 7-27. Frequency Generator Output Waveform

100 kHz Timebase

20 MHz Timebase

Frequency

Output

Timebase

Freq Out

Divisor

(1–16)

Frequency Generator

÷

2

Frequency
Output
Timebase

Freq Out
(Divisor = 5)