beautypg.com

Nortec NHTC User Manual

Page 75

background image

10-20

Page 67
2008-10-01

m

Manual capacity output adjustment range of 20-100%.

n

Humidifier model, capacity, software version.

o

Cylinder model # and capacity rating.

p

Humidifier run time weighted hours.

q

Date and time (year, month, day, hour and minute).

r

Stand by heating to increase steam production response time.

s

Rapid modulation capability reduces response time upon start-up.

t

Short cycling detection and correction diagnostics.

u

Foam detection and correction capability.

v

Scroll through start-up and troubleshooting checklist on graphical display.

w

Self-diagnostics during start-up to system test to prevent unsafe operation
of the unit(s).

x

User adjustable drain/flush frequency.

HUMIDIFIER CONTROLS NHPC

(b) Proportional Controller microprocessor with following features or functions:

1

Graphic function display with user interface with touch type key pad.

2

Acceptance of industry standard [analogue continuous control demand signal
[0-1Vdc] [1-5Vdc] [0-10 Vdc] [2-10 Vdc] [0-16 Vdc] [0-20 mA]

3

Keypad/Display to monitor and control humidifier parameters.

a

System demand in lbs/hr (kg/hr).

b

Security loop status open/close.

c

Control Channel 1 demand %.

d

Manual capacity output adjustment range of 20-100%.

e

Self-diagnostics during start-up to system test to prevent undase
operation of the Unit[s].

f

Control signal type.

g

Software version.

(c)

1

Internal communications via Modbus RTU protocol provides monitoring and
control allowing humidifier(s) to communicate to Building Management
System (BMS). Supporting a RS485 port with a configuration of 9600bps,
8-bits, no parity, one stop bit shall support the following variables:

a

Change Cylinder – Indicates cylinder needs to be replaced (read).

b

Channel 1 Input – Humidifier input value being supplied to channel 0-
100% (read/write).

c

Channel 1 Set point – Control channel 1 setpoint for relative humidity in
space 0-100% (read/write).

d

Channel 2 Input – Humidifier input value being supplied to channel 0-
100% (read/write).

This manual is related to the following products: