beautypg.com

Sensaphone, Cause solution – Phonetics 1108 User Manual

Page 98

background image

Sensaphone

®

Model 1108 User’s Manual

86

Communications / Dial-out:

Problem

1.

The Model 1108 f

ails to dial out.

a)

The telephone number may be

incorrectly programmed.

b)

T

one or pulse (the current dialing

method) is not compatible with the

telephone line on which the Model 1108

is installed.

c)

Recognition

T

ime is too long.

An alert

condition does not remain in ef

fect long

enough to become a valid alarm.

Cause

Solution

Recheck programming steps,

Refer to

Chapter 4, Section 4.2.1.

Switch from the current setting: from tone to

pulse, or from pulse to tone. Refer to

Chapter 4, Section 4.3.

Reprogram Recognition

T

ime. Set the

Recognition

T

ime to the minimum duration

required to create a valid alarm. If possible,

test the new setting by deliberately creating

an alert condition. Refer to Chapter 5,

Section 5.3.

d

)

Max Calls is set to zero.

Reprogram Max Calls. It is a good idea to

set your Max Calls to at least equal the

number of dial-out telephone numbers

programmed. Refer to Chapter 4,