Chapter 5: Alarm Programming

53

In another example, input 5 is configured as a temperature
input. The current temperature is 76 degrees. During a Status
Report:

If disabled, the Model 1108 recites “Number 5—Off

76 degrees—OK.”

If enabled, the Model 1108 recites “Number 5—

76 degrees—OK.”

5.3 Input Recognition Time

The Input Recognition Time is the length of time an alert
condition must be present before a valid alarm exists and dial-
out is activated. This time period is programmable, from 0
minutes, 0 seconds (for immediate response) up to a period of
272 minutes, 0 seconds. If an alert condition begins and then
clears within the established Recognition Time, no dial-out will
occur. When an alert condition continues beyond the pro-
grammed Recognition Time, the Model 1108 initiates dial-out.
The default setting for Input Recognition Time is 0 minutes,
3 seconds.

5.3.1 Programming Input Recognition Time

1.

Press SET.

SET

#

2.

Press RECOGNITION TIME.

RECOGNITION

TIME

7

3.

Press the number (1 to 8) of the selected input to be
programmed.

RECOGNITION

TIME

7

4

1

VOICE

REPS

2

8

INTERCALL

TIME

3

MAX CALLS

CALL

DELAY

CLOCK

TEMP LIMITS

5

CALIBRATE

6

The Model 1108 responds: “Enter minutes.”