Section 402), Nds. (see, Section 402 – Powerware FSS-0342J User Manual
Page 30: Puter, Nds in, When, For pass, Nd. (see, Describes the co, 402 entering commands from a terminal or computer
4
If you change parameter 39 to “Yes,” this command requires the User password.
Page 27
To do this
Use this key sequence
Delete last character typed.
[BACKSPACE] or [CTRL]-[H]
Delete line.
[CTRL]-[X]
Pause displays that take more than one screen.
[CTRL]-[S]
Resume scrolling. (Turn Pause off.)
[CTRL]-[Q]
402 Entering Commands from a Terminal or Computer
To monitor or control FERRUPS from a terminal or computer, simply type in one of the commands and press
[ENTER]. (See the table below.) You can type the command in uppercase or lowercase, and you can use the
whole command or the short form, or you can abbreviate the command as long as you include the letters in the
short form. You can also enter more than one command on a line if you put a semicolon between commands.
Command
Short Form
Password
Function
alarmshelp
ah
None
Shows a list of all possible alarm messages, the audio code and letter
for each alarm and whether the alarm is active.
alarmlog
al
None
Displays Alarm Log. See
alarmtest
at
None
Allows you to test the alarm function. Alarmtest sounds the User
Test alarm (J). See
alarmtest cancel
at c
Turns the User Test alarm off.
chargermode
chm
None
4
Shows the FERRUPS’ battery charger mode. By entering a mode after
the chargermode command, you can change the charger mode:
chargermode off (chm f) or chargermode disable (chm d) = charger
off; chargermode on (chm o) or chargermode enable (chm e) =
charger on; chargermode auto (chm a) = charger enabled if AC input
voltage and battery voltage are acceptable.
clearalarms
ca
None
Clears all active alarms.
clearhistory
ch
None
Clears the minimum and maximum parameter values shown when you
use the extendedhistory or history commands.
clearpassword
cp
None
Clears the current password.
commands
cm
None
Displays a list of all valid commands.
contdisplay
cd
Depends on
parameter
password
Continuously displays the parameter that you are currently displaying.
You can specify other parameters for the continuous display by
entering the name or number of each parameter after the contdisplay
command.
contstatus
cs
None
Continuously displays the Status information. (See the status
command.)
date
da
None
Displays system time and date. To set the date, enter date
[month]/[day]/[year].