If you change parameter 39 to “Yes,” a User password is required for changes.

2

On a FERRUPS control panel, you can display the Ambient Temperature by pressing [DISPLAY] [ . ] or

[DISPLAY] [1] [1] [ENTER].

3

This is a reserved parameter in later model FE 1.8, FE 2.1, FE 3.1 units.

Page 18

Number

Sample Display

Password

Terminal

Name

(Short Form)

Explanation

0

00 Time 07:04:00

None

1

time

(t)

System Time. FERRUPS uses this time to record alarms and inverter runs.

When the DC power has been off and you restart the unit, the time shown will

be the last recorded time before shutdown. Reset time when DC power has

been off.

1

01 V In 120.7

Service

acvoltsin

(vi)

The input voltage FERRUPS is receiving. When this value drops below the

brownout voltage, FERRUPS switches to inverter.

2

02 V Out 120.7

Service

acvoltsout

(vo)

The voltage FERRUPS is providing to your equipment.

3

03 --Reserved--

Reserved

4

04 I Out 3.1

Service

acampsiout

(o)

The current your equipment is drawing from FERRUPS.

5

05 VA Out 374

Change Not

Allowed

vaout

(va)

Volt-Amps Out. The total “apparent power” your equipment is drawing from

FERRUPS. This value is based on parameter 2 multiplied by parameter 4, and

should be less than or equal to the VA or kVA rating of your unit. See

VALimit, parameter 19.

6

06 I Batt 0.0

Service

ibatt

(ib)

Battery Current. When the UPS is running on AC input, this is the charging

current in amps. When the UPS runs on battery power (inverter), this is the

amount of current (in amps) the batteries are supplying to the unit.

7

07 V Batt 48.51

Service

vbatt

(vb)

Battery Volts. The present battery voltage. FERRUPS will alarm if this value

is too low.

8

08 Freq 60.43 Hz

Change Not

Allowed

frequency

(f)

In normal operation, this is the frequency of power FERRUPS is receiving

from the AC input source. If this value falls outside preset limits, FERRUPS

goes to battery power. When FERRUPS is running on battery power, this is

the frequency FERRUPS is supplying to your equipment.

9

09 RunTime 12m

Change Not

Allowed

runtime

(rt)

Estimated Runtime Remaining. The amount of time FERRUPS will continue

to support your equipment when FERRUPS is running on battery power.

FERRUPS will alarm when this value falls below a preset limit.

10

10 Date 06/01/93

None

1

date

(d)

System Date. FERRUPS uses this date to record alarms and inverter runs. The

date must be reset when you restart the unit after DC power is turned off.

. or 11

2

11 Amb Temp 23c

Change Not

Allowed

ambtemp

(at)

The temperature (in Celsius) inside the unit. FERRUPS will alarm and shut

down if this value is too high.

12

3

12 SinkTemp 26c

Change Not

Allowed

heatsinktemp (st) The temperature of the heatsink. FERRUPS will alarm if this value is too

high.

13

13 --Reserved--

Reserved