Best power offers cables for co, Computer db25 to ups – Powerware FSS-0342J User Manual
Page 29
Page 26
Figure 402
Computer DB25 to UPS
2. Connect the cable from the RS232 port on the back of the FERRUPS to the serial port on your terminal or
computer.
3. Your terminal or computer should have these settings:
1200 baud.
8 data bits and 1 stop bit.
No parity.
FULL DUPLEX.
The terminal or terminal emulation software should also be set to FULL DUPLEX. If you are using a
terminal, note that FERRUPS supports the Televideo 900 series, ADM3A and WYSE 50 emulation.
The table below shows the standard settings at the FERRUPS DB25S port and what you can adjust these
settings to. Call the nearest Best Power office if you need to adjust any of the settings.
Specification
Standard Setting
Adjustable to:
Connector
25 pin D (female) wired as DCE.
—
Format
ASCII. 8 data bits. 1 stop bit. Most
significant bit set to 0.
Standard setting or
7/8 bits, ½ stop
Baud Rate
1200
50-38400
Parity
None
Odd, Even or None
Duplex
Full
Full or Half
4. Turn your terminal on or run your terminal emulation software. Then press the [ENTER] key on your
keyboard. You should receive a message from FERRUPS, then a prompt. The prompt will vary depending
on your current password level:
=>
Normal prompt
User=>
User Password has been entered
Press [ENTER] on your keyboard a few times to make sure FERRUPS responds.
5. To control or monitor FERRUPS, simply type the command you need and press [ENTER]. The table on the
next page shows what keystrokes you can use as you type commands or view displays. See
more information on UPS commands.