beautypg.com

Best power offers cables for co, Computer db25 to ups – Powerware FSS-0342J User Manual

Page 29

background image

Page 26

Figure 402

Computer DB25 to UPS

2. Connect the cable from the RS232 port on the back of the FERRUPS to the serial port on your terminal or

computer.

3. Your terminal or computer should have these settings:

1200 baud.

8 data bits and 1 stop bit.

No parity.

FULL DUPLEX.

The terminal or terminal emulation software should also be set to FULL DUPLEX. If you are using a
terminal, note that FERRUPS supports the Televideo 900 series, ADM3A and WYSE 50 emulation.

The table below shows the standard settings at the FERRUPS DB25S port and what you can adjust these
settings to. Call the nearest Best Power office if you need to adjust any of the settings.

Specification

Standard Setting

Adjustable to:

Connector

25 pin D (female) wired as DCE.

Format

ASCII. 8 data bits. 1 stop bit. Most
significant bit set to 0.

Standard setting or

7/8 bits, ½ stop

Baud Rate

1200

50-38400

Parity

None

Odd, Even or None

Duplex

Full

Full or Half

4. Turn your terminal on or run your terminal emulation software. Then press the [ENTER] key on your

keyboard. You should receive a message from FERRUPS, then a prompt. The prompt will vary depending
on your current password level:

=>

Normal prompt

User=>

User Password has been entered

Press [ENTER] on your keyboard a few times to make sure FERRUPS responds.

5. To control or monitor FERRUPS, simply type the command you need and press [ENTER]. The table on the

next page shows what keystrokes you can use as you type commands or view displays. See

Section 402

for

more information on UPS commands.