beautypg.com

Powerware FSS-0342J User Manual

Page 19

background image

Page 16

Letter

Audio

Code

Alarm Message

What It Means

What To Do

A

Low Battery

The battery charge is low because

the system was running on battery

power, or the DC Switch is not on.

The UPS will shut down. Before this alarm, you should

have received a “Low Runtime” alarm (

) to warn

you to shut down your equipment. When AC power

returns, turn FERRUPS on again. The green

CHARGING LED should light as the batteries

recharge.

B

Near Low Battery

The battery voltage has reached the

Near Low Battery setpoint.

The alarm should clear itself when the battery charger

has charged the batteries enough.

C

High Battery

There may be a problem with the

charging circuit or parameter

settings.

Phone Best Power’s Worldwide Service.

D

Low Runtime

The unit is running on battery

power, and the battery runtime

remaining is low.

Do an orderly shutdown of your equipment. Then turn

FERRUPS off to conserve battery power. When AC

input power returns, turn FERRUPS on again.

E

Low AC Output

The output voltage is below a

preprogrammed setpoint.

The UPS will shut down. Shut down your equipment or

bypass the UPS, and turn the UPS switch off. Phone

Best Power’s Worldwide Service.

F

High AC Output

The output voltage is higher than

the alarm setting.

Phone Best Power’s Worldwide Service.

G

– –

Output Overload

Your equipment is drawing more

volt-amps (power) than the UPS

can provide. (See your model’s

VA rating.) The unit will continue

to run with overloads as high as

125% for 10 minutes and then shut

down.

Reduce the amount of equipment using FERRUPS

power and turn FERRUPS on again. If the problem

persists, phone Best Power’s Worldwide Service.

H

Hi Ambient Temp

The temperature inside the unit is

too high. If the temperature

reaches a preset point, the unit will

shut down.

If the UPS has shut down, call Best Power’s

Worldwide Service. If not, shut down the protected

equipment and FERRUPS, correct the cause of the high

temperature if possible, and turn FERRUPS on again.

If the problem persists, phone Best Power’s Worldwide

Service.

I

Hi Heatsink Temp

The inverter temperature is too

high. If the temperature reaches a

preset point, the UPS will shut

down.

If the UPS has shut down, call Best Power’s

Worldwide Service. If not, shut down your equipment

or bypass the UPS; turn the UPS off. Phone Best

Power’s Worldwide Service.

J

– – –

User Test Alarm

The user is testing the alarm

feature.

To start the user test alarm from the control panel, press

[CONTROL] [8] [ENTER] [ENTER]. Repeat the

procedure to turn the alarm off.

K

Hi Transfmr Temp

The transformer temperature is too

high. If the temperature reaches a

preset point, the UPS will shut

down.

The UPS may have shut down; if so, call Best Power’s

Worldwide Service. If the UPS has not shut down, shut

down your equipment or bypass the UPS; then, turn the

UPS off and call Best Power’s Worldwide Service.

L

Check Charger

The UPS has detected a charger

problem.

Phone Best Power’s Worldwide Service.