Number

Sample Display

Password

Terminal

Name

(Short Form)

Explanation

Page 19

14

14 XfmrTemp 28c

Change Not

Allowed

xfmrtemp

(xt)

The temperature of the transformer. FERRUPS will alarm and shut down if

this value is too high. This parameter is only active on some models; for

other models, the display always shows -63c.

15

15 Unit ID

Network #1 UPS

None

(See note 1

on page 18.)

unitident

(id)

Unit ID. An identification string that can be configured for use with your

network.

16

16 FullLoad% 075

Change Not

Allowed

fullload

(l)

Percent of Full Load. The percentage of FERRUPS’ total capacity that is

actually being used by your equipment.

17

17 Watts 374

Change Not

Allowed

watts

(w)

The total “real power” your equipment is drawing from FERRUPS.

18

18 PF 0.73 Dist

Change Not

Allowed

powerfact

(pf)

The power factor of your equipment; the difference in the way it draws

voltage and current. Power factor is equal to Watts Out (parameter 17)

divided by VA Out (parameter 5). This parameter also tells whether the power

factor is leading (Lead), lagging (Lag), or distortion (Dist).

19

19 VALimit 500

Change Not

Allowed

valimit

(val)

The maximum volt-amps FERRUPS can supply to your equipment at the

present power factor. The unit will alarm when VA Out (parameter 5) is

higher than this value.

20

20 #PwrOut 1

Change Not

Allowed

powerout

(po)

The number of times there has been a loss of input power since you started

the unit.

21

21 #OvrLds 0

Change Not

Allowed

overloads

(ol)

The number of times FERRUPS has sensed an overload; that is, the number

of times VA Out has been greater than VA Limit.

22

22 SysHrs 00000

Change Not

Allowed

syshours

(sh)

The total number of hours FERRUPS has been operating, regardless of mode.

This number does not increase while the On/Off switch is turned off.

23

23 InvMin 0000.0

Change Not

Allowed

invmin

(im)

The total number of minutes the inverter has run since startup.

24

24 Inverter Log

L 0319 2127 1215

Change Not

Allowed

inverterlog

(il)

A record of the date, time, duration and reason for the last 20 inverter (battery

power) runs. (See

Section 306.

)

25

25 Alarm Log

A 0319 2127 1215

Change Not

Allowed

alarmlog

(al)

A record of the date, time, duration and reason for the last 20 alarms. (See

Section 306

.)

26

26 Test Results

(See explanation.)

Change Not

Allowed

testresults

(tr)

This parameter records the results of the last system test. The parameter

display includes the time and date of the test and the results of each part of the

system test. (

See Section 303

.)

Additional Parameters: The microprocessor in your FERRUPS keeps track of more than 100 parameters.
Parameters 27 and above are alarm and operation set points, calibration factors and other settings. You usually do not
need access to these parameters for normal operation of the FERRUPS. If you need information about the full range
of FERRUPS parameters, call Best Power’s Worldwide Service to ask for TIP 407 or TIP 503. TIP 407 describes
communication from a control panel. TIP 503 describes communication through the RS232 port.