Troubleshooting – Lochinvar ARMOR 151 - 801 User Manual

Page 35

background image

Service Manual

35

3

Troubleshooting

(continued)

Table 3F (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Water Heater Interface

FAULT

DESCRIPTION

CORRECTIVE ACTION

Low 24 VAC

120 VAC input to the main control board has
dropped below 80 VAC.

• Check 120 VAC supply to the transformer.

• Check wiring connections at the low voltage terminal

strip.

• Check the wire size/length to remote devices.

• Replace the transformer.

Watch Dog Error

The main control board has detected an
internal fault.

• Replace the main control board.

Write EEProm

The main control board has detected an
internal fault.

• Replace the main control board.

CRC Parameters

The main control board has detected an
internal fault.

• Replace the main control board.

No Error Stored

The main control board has detected an
internal fault.

• Replace the main control board.

Fatal Error

Parameters

The main control board has detected an
internal fault.

• Restore the default parameters.
• Replace the main control board.
• Replace the display board.