Troubleshooting – Lochinvar ARMOR 151 - 801 User Manual
Page 25
25
Service Manual
3
Troubleshooting
(continued)
Table 3A Troubleshooting Chart - No Display
FAULT
CAUSE
CORRECTIVE ACTION
No Display
- No 120 VAC supplied to unit.
• Check external line switch, fuse, or breaker.
• Check position of ON/OFF switch. Turn switch to the
ON position.
• Check 120 VAC through the ON/OFF switch.
• Check wiring harness connection between display
board and main control board. Connect
harness at both points.
- No voltage through the switch.
• Replace switch.
- Bad display board.
• Replace board.
- Bad main control board.
• Replace the main control board.
- Blown fuse.
• Replace fuse F3 on the main control board, see
page 24 of this manual.
No Burner
Operation
- Main control board temperature set point
satisfied.
• Review temperature setting.
- Remote thermostat satisfied.
• Review remote thermostat setting.
- Unit locked out on fault.
• Consult display for specific fault. Refer to fault
descriptions on pages 28 - 35 of this manual for
corrective actions.
Unit Does Not
Modulate Above
50%
- Water heater controlled by BMS.
• Check BMS parameter settings. Optional PC software
required.
- Flue sensor open.
• Verify that the flue sensor is located in the flue outlet.
• Check wiring connections at the flue sensor.
• Check the resistance of the flue sensor and compare
to Table 3D on page 26 of this manual.