Table 3F (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Water Heater Interface

FAULT

DESCRIPTION

CORRECTIVE ACTION

Flame Sequence

(will require a manual

reset once the condition

has been corrected. Press

the RESET button on the
SMART SYSTEM display

to reset.)

The flame detector circuit is seeing a flame
signal while no flame is present.

• Check supply voltage for proper polarity.

• Check external wiring for voltage feedback.

• Check the flame rod and make sure it is clean.

• Check the internal wiring for bad connections.

• Replace main control board.

Auto Reset

High Limit

The outlet water temperature has exceeded
the setting of the automatic reset high limit.

• Verify that the system is full of water and that all air

has been properly purged from the system.

• Verify that the water heater is piped properly into the

heating system. Refer to Section 6 - Hydronic Piping
of the Armor Installation and Operation Manual
for the proper piping methods for the Armor water
heater.

• Check 120 vac to water heater pump motor on a call

for heat. If voltage is not present, check wiring back
to the main control board.

• Replace the main control board if necessary.

• If 120 vac is present on a call for heat and the water

heater pump is not operating, replace the pump.

• If the system pump is a variable speed pump, ensure

that the system flow is not less than the water heater
flow.

• If operating on something other than an outlet sensor,

check temperature setting of the main control board.

• If the manual reset high limit has tripped, check

setting of the device.

• Check resistance of water sensors and compare to

Table B on page 26 of this manual. Replace
sensor if necessary.

• Replace high limit.

Manual Reset

High Limit

(will require a manual

reset once the condition

has been corrected. Press

the RESET button on the
SMART SYSTEM display

to reset.)

The outlet water temperature has exceeded
the fixed setting of the manual reset high
limit.

• Verify that the system is full of water and that all air

has been properly purged from the system.

• Verify that the water heater is piped properly into the

heating system. Refer to Section 6 - System Piping
of the Armor Water Heater Installation and Operation
Manual for the proper piping methods for the Armor
water heater.

• Check 120 VAC to water heater pump motor on a call

for heat. If voltage is not present, check wiring back
to the main control board.

• Replace the main control board if necessary.

• If 120 VAC is present on a call for heat and the water

heater pump is not operating, replace the pump.

• If the manual reset high limit has tripped, check

setting of the device.

• Check resistance of water sensors and compare to

Table 3C on page 26 of this manual. Replace sensor
if necessary.

• Replace high limit.