Troubleshooting – Lochinvar ARMOR 151 - 801 User Manual

Page 34

background image

3

Troubleshooting

34

Service Manual

Table 3F (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Water Heater Interface

FAULT

DESCRIPTION

CORRECTIVE ACTION

Outlet Temp High

Outlet water temperature has exceeded the
maximum outlet water temperature.

• Verify that the system is full of water and that all air

has been properly purged from the system.

• Verify that the water heater is piped properly into the

heating system. Refer to Section 6 - System Piping
of the Armor Water Heater Installation and Operation
Manual for the proper piping methods for the Armor
water heater.

• Check for 120 VAC to the water heater pump motor on

a call for heat. If voltage is not present, check wiring
back to the main control board. Replace the main
control board if necessary.

• If 120 VAC is present on a call for heat and the water

heater pump is not operating, replace the pump.

• Replace the main control board.

Rem Ctrl Flt

External control is cycling too often.

• Check set point of the external control.

• Check the wiring between the external control and the

unit.

• Replace the control.

Service Blk

While the unit is in Service Mode, the outlet
temperature has exceeded 185°F.

• Establish a heating load to remove the heat from the

water heater loop.

• Verify that the system is full of water and that all air

has been properly purged from the system.

• Verify that the water heater is piped properly into the

heating system. Refer to Section 6 - System Piping
of the Armor Water Heater Installation and Operation
Manual for the proper piping methods for the Armor
water heater.

• Check 120 VAC to the water heater pump motor on a

call for heat. If voltage is not present, check the wiring
back to the main control board. Replace the main
control board if necessary.

• If 120 VAC is present on a call for heat and the water

heater pump is not operating, replace the pump.

• Verify that the water heater pump is set to the proper

speed or that the water heater pump is the proper
size. Reference Section 6 - System Piping of the
Armor Water Heater Installation and Operation
Manual for water heater pump specifications.