Specifications (continued) – Liebert UPSTATION GXT 2U User Manual
Page 33

29
SPECIFICATIONS (CONTINUED)
Model Number
GXT2-2000RT120
GXT2-3000RT120
Model Rating
2000VA / 1400W
3000VA / 2100W
DIMENSIONS in (mm)
Unit
W x D x H in. (mm)
3.5 x 21.5 x 17
(87 x 547 x 430)
3.5 x 24.2 x 17
(87 x 618 x 430)
Shipping
W x D x H in. (mm)
10.5 x 27.2 x 23
(268 x 692 x 585)
10.5 x 27.2 x 23
(268 x 692 x 585)
WEIGHT lbs (kg)
Unit
54 (24)
69 (31)
Shipping
62.6 (28.4)
78.0 (35.4)
INPUT AC PARAMETERS
Voltage Range
(typical)
120 VAC nominal; variable based on output load
100% - 90% loading
90 VAC / 140 VAC
90 VAC / 140 VAC
90% -70% loading
80 VAC / 140 VAC
80 VAC / 140 VAC
70% -30% loading
70 VAC / 140 VAC
70 VAC / 140 VAC
30% - 0% loading
60 VAC / 140 VAC
60 VAC / 140 VAC
Frequency
40 - 70 Hz; Auto Sensing
Input Power Cord
10 ft. attached
w/ NEMA 5-20 plug
10 ft. attached
w/ NEMA L5-30 plug
OUTPUT AC PARAMETERS
Output Receptacles
(4) 5-20R T-Slot,
accepts 15A plug
(4) NEMA 5-15R
(1) NEMA L5-30R on 12 in cord
Voltage
100/110/115/120/127 (user configurable) VAC; ±3%
Frequency
50 Hz or 60 Hz
Waveform
Sinewave
Main Mode
Overload
200% for 8 cycles; 130% for 10 seconds with transfer to bypass
BATTERY PARAMETERS
Type
Valve-regulated, nonspillable, flame retardant, lead acid
Qty x V x Rating
4 x 12V x 9.0 AH
6 x 12V x 9.0 AH
Battery Mfg / Part #
Panasonic / UP-VW1245P1
Yuasa / REW 45-12 FR
Back-up Time
Recharge Time
5 hours to 95% capacity after full discharge into 100% load
ENVIRONMENTAL
Operating Temp
+32°F to +104°F (0°C to +40°C)
Storage Temp
+5°F to +122°F (-15°C to +50°C)
Relative Humidity
0% to 95%, non-condensing
Operating Elevation
Up to 10,000 ft. (3000m) at 104°F (40°C) without derating
Storage Elevation
50,000 ft. (15,000 m) maximum
Audible Noise
<55 dBA, at 1 meter from the rear
<50 dBA, at 1 meter from the front or sides
AGENCY
Safety
UL 1778, c-UL Listed (Suitable for computer room applications)
RFI/EMI
FCC Part 15, Subpart B, Class A
Surge Immunity
IEEE/ANSI C62.41 Category A & B
Transportation
ISTA Procedure 1A