Specifications, Pecifications – Liebert UPSTATION GXT 2U User Manual
Page 32

28
SPECIFICATIONS
Model Number
GXT2-700RT120
GXT2-1000RT120
GXT2-1500RT120
Model Rating
700VA / 490W
1000VA / 700W
1500VA / 1050W
DIMENSIONS in (mm)
Unit
W x D x H in. (mm)
3.5 x 21.5 x 17
(87 x 547 x 430)
3.5 x 21.5 x 17
(87 x 547 x 430)
3.5 x 21.5 x 17
(87 x 547 x 430)
Shipping
W x D x H in. (mm)
10.4 x 27.3 x 22.5
(268 x 692 x 585)
10.4 x 27.3 x 22.5
(268 x 692 x 585)
10.4 x 27.3 x 22.5
(268 x 692 x 585)
WEIGHT lbs (kg)
Unit
48.9 (22.2)
49.1 (22.3)
50.6 (23)
Shipping
57.7 (26.2)
57.9 (26.3)
59.5 (27)
INPUT AC PARAMETERS
Voltage Range
(typical)
120 VAC nominal; variable based on output load
100% - 90% loading
80 VAC / 140 VAC
80 VAC / 140 VAC
90 VAC / 140 VAC
90% -70% loading
80 VAC / 140 VAC
80 VAC / 140 VAC
80 VAC / 140 VAC
70% -30% loading
70 VAC / 140 VAC
70 VAC / 140 VAC
70 VAC / 140 VAC
30% - 0% loading
60 VAC / 140 VAC
60 VAC / 140 VAC
60 VAC / 140 VAC
Frequency
40 - 70 Hz; Auto Sensing
Input Power Cord
6 ft. attached
w/ NEMA 5-15 plug
10 ft. attached
w/ NEMA 5-15 plug
10 ft. attached
w/ NEMA 5-15 plug
OUTPUT AC PARAMETERS
Output Receptacles
(4) NEMA 5-15R
Voltage
100/110/115/120/127 (user configurable) VAC; ±3%
Frequency
50 Hz or 60 Hz
Waveform
Sinewave
Main Mode
Overload
200% for 8 cycles; 130% for 10 seconds with transfer to bypass
BATTERY PARAMETERS
Type
Valve-regulated, nonspillable, flame retardant, lead acid
Qty x V x Rating
4 x 12V x 7.0 or 7.2 AH
Battery Mfg / Part #
China Storage Battery / CSB FR 1270 F2
Back-up Time
Recharge Time
5 Hours to 95% capacity after full discharge into 100% load
ENVIRONMENTAL
Operating Temp
+32°F to +104°F (0°C to +40°C)
Storage Temp
+5°F to +122°F (-15°C to +50°C)
Relative Humidity
0% to 95%, non-condensing
Operating Elevation
Up to 10,000 ft. (3000m) at 104°F (40°C) without derating
Storage Elevation
50,000 ft. (15,000m) maximum
Audible Noise
<50 dBA, at 1 meter from the rear
<45 dBA, at 1 meter from the front or sides
AGENCY
Safety
UL 1778, c-UL Listed (Suitable for computer room applications)
RFI/EMI
FCC Part 15, Subpart B, Class A
Surge Immunity
IEEE/ANSI C62.41 Category A & B
Transportation
ISTA Procedure 1A