A-2

INSTALLATION

INVERTEC V250-S

A-2

Height

Width

Depth

Weight

15.0 in.

9.1 in.

19.7 in.

36 lbs.

381 mm

231 mm

500 mm

17 Kg

PHYSICAL DIMENSIONS

THREE PHASE

SINGLE PHASE

Standard

Input Current

Voltage

at Rated Output

Model

208/230/460 34/32/16

60Hz

200/220/400/440 35/33/18/17

50/60

Hz

Volts at

Duty Cycle

(1)

Amps

Rated Amps

Model

35% Duty Cycle

250

30

60Hz

60% Duty Cycle

200

28-32

60Hz

100% Duty Cycle

165

26.5

60Hz

35% Duty Cycle

250

28†-30

50/60Hz

60% Duty Cycle

200

29-32

50/60Hz

100% Duty Cycle

165

26.5

50/60Hz

Welding

Constant Open

Current Range

Circuit Voltage

1-250 Amps

65-80 VDC

Standard

Input Current

Voltage

at Rated Output

Model

208/230/460 60Hz

59/57/29

60Hz

200/220/400/440 50/60 Hz

58/58/30/30

50/60 Hz

Volts at

Duty Cycle

(1)

Amps

Rated Amps

Model

35% Duty Cycle

250

27†-30

60Hz

60% Duty Cycle

200

28-32

60Hz

100% Duty Cycle

165

26.5

60Hz

35% Duty Cycle

250

26†-30

50/60Hz

60% Duty Cycle

200

28-32

50/60Hz

100% Duty Cycle

165

26.5

50/60Hz

Welding

Constant Open

Current Range

Circuit Voltage

1-250 Amps

65-80 VDC

INPUT

RECOMMENDED INPUT WIRE AND FUSE SIZES

Type 75°C

Type 75°C

Copper

Fuse

Input

Copper

Ground

(Superlag)

Ampere

Wire in

Wire in

Input

or

Rating

Conduit

Conduit

Voltage

Breaker

on

AWG (IEC)

AWG (IEC)

Frequency

(2)

Size

Nameplate

Sizes

Sizes

208/60

50

34

10 (6mm

2

)

10 (6mm

2

)

230/60

50

32

10(6mm

2

)

10 (6mm

2

)

460/60

30

16

10 (6mm

2

)

10 (6mm

2

)

200/50/60

50

35

10 (6mm

2

)

10 (6mm

2

)

220/50/60

50

33

10 (6mm

2

)

10 (6mm

2

)

400/50/60

30

18

10 (6mm

2

)

10 (6mm

2

)

440/50/60

30

17

10 (6mm

2

)

10 (6mm

2

)

Type 75°C

Type 75°C

Copper

Fuse

Input

Copper

Ground

(Superlag)

Ampere

Wire in

Wire in

Input

or

Rating

Conduit

Conduit

Voltage

Breaker

on

AWG (IEC)

AWG (IEC)

Frequency

(2)

Size

Nameplate

Sizes

Sizes

208/60

(3)

80

59

8 (10mm

2

)

10 (6mm

2

)

230/60

(3)

80

57

8 (10mm

2

)

10 (6mm

2

)

460/60

40

29

10 (6mm

2

)

10 (6mm

2

)

200/50/60

80

58

8 (16mm

2

)

10 (6mm

2

)

220/50/60

80

58

8 (16mm

2

)

10 (6mm

2

)

400/50/60

40

30

10 (6mm

2

)

10 (6mm

2

)

440/50/60

40

30

10 (6mm

2

)

10 (6mm

2

)

THREE PHASE

SINGLE PHASE

THREE PHASE

SINGLE PHASE

THREE PHASE

SINGLE PHASE

OUTPUT

RATED OUTPUT

(1)

Based on a 10 min. period.

(2) Input voltage must be within ±10% of rated value.

(3)

For 1 phase use on 208 or 230 VAC input with output usage above 175A/60% or 200A/35%, the #10 input line cord supplied with the unit should be changed to a

#8 or larger conductor cord.

(†) 200 & 208VAC input may not meet NEMA/IEC specifications at 250 Amps.

Technical Specifications - Invertec V250-S