beautypg.com

The tests detailed in, Table f.2, Troubleshooting & repair – Lincoln Electric INVERTEC V250-S User Manual

Page 49: Input rectifier test (continued)

background image

F-17

TROUBLESHOOTING & REPAIR

F-17

6. If the Input Rectifier does not meet

the acceptable readings outlined in
Table F.2. the component may be
faulty. Replace.

Note: Before replacing the Input

Rectifier(D9) check the input
power switch (S1) and perform
the

Power Board Resistance

Test. Also check for leaky or
faulty filter capacitors.

7.

When installing a new Input
Rectifier, torque the mounting nuts to
44IN-LBS. A thin coating of Dow
Corning 340 Heat Sink Compound
(Lincoln E1868) is recommended.
Torque the lead terminals to 31IN-
LBS. See

Input Rectifier Bridge

Removal And Replacement.

8. If the Input Rectifier is good be sure

to reconnect leads #207, #207A and
#209 to the correct terminals and
torque to 31IN-LBS. See wiring dia-
gram and Figure F.2.

INPUT RECTIFIER TEST (continued)

INVERTEC V250-S

Return to Section TOC

Return to Section TOC

Return to Section TOC

Return to Section TOC

Return to Master TOC

Return to Master TOC

Return to Master TOC

Return to Master TOC

TEST POINT TERMINALS

ANALOG METER X10 RANGE

+ Probe

- Probe

Acceptable Meter Readings

A

207

Greater than 1000 ohms

B

207

Greater than 1000 ohms

C

207

Greater than 1000 ohms

A

209

Less than 100 ohms

B

209

Less than 100 ohms

C

209

Less than 100 ohms

207

A

Less than 100 ohms

207

B

Less than 100 ohms

207

C

Less than 100 ohms

209

A

Greater than 1000 ohms

209

B

Greater than 1000 ohms

209

C

Greater than 1000 ohms

TABLE F.2 Input Rectifier Test Points