Determine boiler location, Installation & operation manual – Lochinvar 1 User Manual
Page 8
Installation & Operation Manual
8
6" (152 40 MM)
24" (610 MM)
REAR
0"
LEFT
OPEN FRONT
13" (330 MM)
TOP
0"
RIGHT
1/4” (6 MM) MINIMUM CLEARANCE
AROUND HOT WATER PIPES
1” (25 MM) MINIMUM CLEARANCE
AROUND VENT PIPES
Figure 1-2 Alcove Installation - Minimum Required Clearances
6" (152 MM)
FRONT
4" (330 MM)
TOP
0"
LEFT
0"
RIGHT
24" (610 MM)
REAR
6" (152 MM)
VENTILATING*
AIR OPENING
VENTILATING*
AIR OPENING
CLOSED DOOR
*AREA OF EACH OPENING:
1 SQ. INCH PER 1000 BTU PER HOUR INPUT
WITH A MINIMUM OF 100 SQ. INCHES
1/4” (6 MM) MINIMUM CLEARANCE
AROUND HOT WATER PIPES
1” (25 MM) MINIMUM CLEARANCE
AROUND VENT PIPES
Figure 1-1 Closet Installation - Minimum Required Clearances
ƽ WARNING
For closet installations, CPVC or
stainless steel material MUST BE
used in a closet structure due to
elevated temperatures. Failure to
follow this warning could result in
fire, personal injury, or death.
RECOMMENDED SERVICE
CLEARANCES:
Front
- 30" (762 mm)
Top
- 24" (610 mm)
Left Side - 24" (610 mm)
Rear - 24" (610 mm)
1
Determine boiler location
RECOMMENDED SERVICE
CLEARANCES:
Front
- 30" (762 mm)
Top
- 24" (610 mm)
Left Side - 24" (610 mm)
Rear - 24" (610 mm)
ƽ WARNING
For alcove installations, CPVC or
stainless steel material MUST BE
used in an alcove structure due to
elevated temperatures. Failure to
follow this warning could result in
fire, personal injury, or death.