Gas connections, Connecting gas supply piping – Lochinvar 1 User Manual
Page 34

34
Installation & Operation Manual
6
Gas connections
Connecting gas supply piping
1. Refer to FIG. 6-1 to pipe gas to the boiler.
 
a. Install ground joint union for servicing, when 
 
required.
b. In Canada – When using manual main shutoff 
 
valves, it must be identified by the installer.
2. Install sediment trap / drip leg.
Figure 6-1 Gas Supply Piping
3. Support piping with hangers, not by the boiler or its
accessories.
Do not check for gas leaks with an open 
flame – use the bubble test. Failure to 
use the bubble test or check for gas leaks 
can cause severe personal injury, death, or 
substantial property damage.
4. Purge all air from the gas supply piping.
5. Before placing the boiler in operation, check the boiler
and its gas connection for leaks.
a. The appliance must be disconnected from the gas 
 
supply piping system during any pressure testing of
that system at a test pressure in excess of 1/2 PSIG
(3.5 kPa).
b. The appliance must be isolated from the gas supply
piping system by closing a manual shutoff valve
during any pressure testing of the gas supply piping
system at test pressures equal to or less than 1/2 PSIG
(3.5
kPa).
c. The appliance and its gas connection must be leak
tested before placing it in operation.
The gas valve and blower will not support 
the weight of the piping. Do not attempt 
to support the weight of the piping with 
the boiler or its accessories. Failure to 
comply could result in severe personal 
injury, death, or substantial property 
damage.
ƽ WARNING
ƽ WARNING
6. Use pipe sealing compound compatible with propane
gases. Apply sparingly only to male threads of the pipe 
joints so that pipe dope does not block gas flow.
UNION
GAS SUPPLY
DRIP LEG
MANUAL SHUTOFF
VALVE
(FIELD SUPPLIED)
10 FT
(RECOMMENDED
10 LINEAR FEET
WHERE POSSIBLE)
Failure to apply pipe sealing compound as 
detailed in this manual can result in severe 
personal injury, death, or substantial 
property damage.
ƽ WARNING
ƽ WARNING Ensure that the high gas pressure regulator
is at least 10 feet (3 m) upstream of the 
appliance.
