4

The Knight Wall Mount Boiler - How it works...

1. Stainless steel heat exchanger

Allows system water to flow through specially designed

coils for maximum heat transfer, while providing

protection against flue gas corrosion. The coils are

encased in a jacket that contains the combustion process.

2. Combustion

chamber

access

cover

Allows access to the combustion side of the heat

exchanger

coils.

3. Blower

The blower pulls in air and gas through the venturi (item

5). Air and gas mix inside the blower and are pushed into the

burner, where they burn inside the combustion chamber.

4. Gas

valve

The gas valve senses the negative pressure created by the

blower, allowing gas to flow only if the gas valve is

powered and combustion air is flowing.

5. Venturi

The venturi controls air and gas flow into the burner.

6. Flue gas sensor (limit rated)

This sensor monitors the flue gas exit temperature. The control

module will modulate and shut down the boiler if flue gas

temperature gets too hot. This protects the flue pipe from

overheating.

7. Boiler outlet temperature sensor (housed with high
limit

sensor)

This sensor monitors boiler outlet water temperature (system

supply). If selected as the controlling sensor, the control

module adjusts boiler firing rate so the outlet temperature is

correct.

8. Boiler

inlet

temperature

sensor

This sensor monitors return water temperature (system

return). If selected as the controlling sensor, the control

module adjusts the boiler firing rate so the inlet temperature is

correct.

9. Temperature and pressure gauge (field installed, not
shown)

Monitors the outlet temperature of the boiler as well as the

system water pressure.

10. Electronic LCD display

The electronic display consists of 4 buttons, a navigation dial

and a multiple line liquid crystal display.

11. Flue pipe adapter

Allows for the connection of the PVC vent pipe system to the

boiler.

12. Burner (not shown)

Made with metal fiber and stainless steel construction,

the burner uses pre-mixed air and gas and provides a

wide range of firing rates.

13. Water outlet (system supply)

The water outlet is the water connection for water leaving the

boiler and entering the system. Boiler connection is 1".

14. Water inlet (system return)

The water inlet is the water connection for water entering the

boiler from the system. Boiler connection is 1".

15. Gas connection pipe

Threaded pipe connection of 1/2". This pipe should be

connected to the incoming gas supply for the purpose of

delivering gas to the boiler.

16. SMART SYSTEM Control Module

The SMART SYSTEM Control responds to internal and

external signals and controls the blower, gas valve, and pumps

to meet the heating demand.

17. Air intake adapter

Allows for the connection of the PVC air intake pipe to

the

boiler.

18. High voltage junction box

The junction box contains the connection points for the line

voltage power and all pumps.

19. Manual air vent

Designed to remove trapped air from the heat exchanger

coils.

20. Low voltage connection board

The connection board is used to connect external low voltage

devices.

21. Low voltage wiring connections (knockouts)

Conduit connection points for the low voltage
connection

board.

22. Condensate drain connection

Connects the condensate drain line to a 1/2" pipe.

23. Access door

Provides access to all internal components.

24. Ignition electrode

Provides direct spark for igniting the burner.

25. Flame inspection window

The quartz glass window provides a view of the burner

surface and flame.

26. Gas shutoff switch

An electrical switch designed to cut power to the gas valve to

prevent releasing any gas.

27. High limit sensor (housed with outlet sensor)

Device that monitors the outlet water temperature. If the

temperature exceeds its setting, it will break the control circuit,

shutting the boiler down.

28. Relief valve

Protects the heat exchanger from an over pressure condition.

The relief valve provided with the unit is set at 30 psi.

29. Flame sensor

Used by the control module to detect the presence of burner

flame.

30. Line voltage wiring connections (knockouts)

Conduit connection points for the high voltage junction box.

31. Air pressure switch

The air pressure switch detects blocked inlet conditions.

32. Transformer

The transformer provides 24V power to the integrated control.