General venting, Requirements for installation in canada, Sizing – Lochinvar Knight Wall Mount Soiler 51-211 User Manual

Page 16

background image

3

General venting

16

Installation & Operation Manual

Requirements for installation in

Canada

1. Installations must be made with a vent pipe system

certified to ULC-S636.

IPEX is an approved vent manufacturer in Canada

supplying vent material listed to ULC-S636.

2. The first three (3) feet of plastic vent pipe from the

appliance flue outlet must be readily accessible for visual

inspection.

3. The components of the certified vent system must not be

interchanged with other vent systems or unlisted

pipe/fittings.

4. The 2" and 3" Concentric Vent Kits available from

Lochinvar (see Section 4 – Sidewall Termination – Optional

Concentric

Vent) and the 2" and 3" Concentric Vent Kits

available from IPEX are approved for use on the Knight

wall mount boiler. Both kits are listed to the ULC-S636

standard for use in Canada.

Minimum / Maximum allowable

combustion air and vent piping lengths

are as follows:

Combustion Air = 12 equivalent feet minimum / 100
equivalent feet maximum

Vent = 12 equivalent feet minimum / 100 equivalent feet
maximum

When determining equivalent combustion air and vent
length, add 5 feet for each 90° elbow and 3 feet for each
45° elbow.

EXAMPLE: 20 feet of PVC pipe + (4) 90° elbows + (2)
45° elbows + (1) concentric vent kit (CVK3003) = 49
equivalent feet of piping.

The appliance output rating will reduce
by up to 1.5% for each 25 feet of vent
length.

NOTICE

Model Kit Number

Equivalent Vent

Length

51 - 106

CVK3008

3 feet

51 - 211

CVK3003

3 feet

Table 3B Concentric Vent Kit Equivalent Vent Lengths

Sizing

The Knight wall mount boiler uses model specific combustion
air intake and vent piping sizes as detailed in Table 3A below.

Model

2" Max Vent/Air

3" Max Vent/Air

51

40 feet

100 feet

81

40 feet

100 feet

106

40 feet

100 feet

151

N/A

100 feet

211

N/A

100 feet

Table 3A Maximum Combustion Air and Vent Piping
Lengths

NOTICE

Increasing or decreasing combustion air or
vent piping sizes is not authorized.