General, Venting – Lochinvar Knight Wall Mount Soiler 51-211 User Manual

Page 20

background image

20

3

General

venting

Installation & Operation Manual

The installer must use a specific vent
starter adapter at the flue collar
connection. The adapter is supplied by
the vent manufacturer to adapt to its vent
system. See Table 3F for approved vent
adapters. Discard CPVC starter piece.

NOTICE

All vent connections MUST be secured by
the vent manufacturer's joint connector
(FIG. 3-8).

NOTICE

IMG00155

JOINT CONNECTOR REQUIRED
AT ALL COMPONENT CONNECTIONS
OF VENT SYSTEM

POLYPROPYLENE ADAPTER
W/FLUE CLAMP

Figure 3-8 Near Boiler Polypropylene Venting

Model

Centrotherm InnoFlue SW

Duravent Polypro

Polypropylene Adapter /

Flue Clamp

Joint

Connector

Sidewall Retaining

Bracket*

Sidewall

Adapter*

Polypropylene Adapter

Joint

Connector

Sidewall Kit*

51-106

ISAG0202 w/IAFC02

IANS02

IATP0202

ISTAGL0202 2PPS-AD w/ PPS-PAC 2PPS-LB

2PPS-HLK

151-211

ISAG0303 w/IAFC03

IANS03

IATP0303

ISTAGL0303 3PPS-AD w/ PPS-PAC 3PPS-LB

3PPS-HLK

* These parts are only needed if the sidewall termination assembly is used (see FIG. 4-4B on page 24).

Table 3F Approved PolypropyleneTerminations

Polypropylene

This product has been approved for use with polypropylene
vent with the manufacturers listed in Table 3E.

All terminations must comply with listed options in this manual
and be a single-wall vent offering.

For use of flex pipe, it is recommended to have the vent material
in 32°F or higher ambient space before bending at installation.
No bends should be made to greater than 45° and ONLY
installed in vertical or near vertical installations.

For support and special connections required, see the
manufacturer's instructions. All vent is to conform to standard
diameter and equivalent length requirements established.

Use only the adapters and vent system listed
in Tables 3E and 3F. DO NOT mix vent
systems of different types or manufacturers.
Failure to comply could result in severe
personal injury, death, or substantial
property damage.

ƽ WARNING

Installations must comply with applicable
national, state, and local codes. For
Canadian installation, polypropylene vent
must be listed as a ULC-S636 approved
system.

NOTICE

Installation of a polypropylene vent system
should adhere to the vent manufacturer’s
installation instructions supplied with the
vent system.

NOTICE

Approved Polypropylene Vent Manufacturers

Make

Model

Centrotherm Eco Systems

InnoFlue SW/Flex

Duravent (M & G Group)

PolyPro Single-Wall / PolyPro Flex

Table 3E Polypropylene Vent Pipe and Fittings

ƽ WARNING

Insulation should not be used on
polypropylene venting materials. The use
of insulation will cause increased vent wall
temperatures, which could result in vent
pipe failure.