beautypg.com

Sidewall direct venting – Lochinvar Knight Wall Mount Soiler 51-211 User Manual

Page 28

background image

28

Installation & Operation Manual

4

Sidewall direct venting

Sidewall termination – optional concentric vent

Multiventing sidewall terminations

When two (2) or more direct vent appliances are vented near
each other, each appliance must be individually vented (see FIG.
4-11). NEVER common vent or breach vent this appliance.
When two (2) or more direct vent appliances are vented near
each other, two (2) vent terminations may be installed as shown
in FIG. 4-11. It is important that vent terminations be made as
shown to avoid recirculation of flue gases.

VENT

COMBUSTION
AIR

12"
MINIMUM

Figure 4-11 Concentric Vent and Combustion Air Termination

Figure 4-10 Concentric Vent Sidewall Attachment

DO NOT use field-supplied couplings to
extend pipes. Airflow restriction will occur
and may cause intermittent operation.

8. Cement appliance combustion air and vent pipes to the

concentric vent termination assembly. See FIG. 4-10 for
proper pipe attachment.

9. Operate the appliance one (1) heat cycle to ensure

combustion air and vent pipes are properly connected to
the concentric vent termination connections.

CAUTION