All vent pipes and air inlets must terminate
at the same height to avoid possibility of
severe personal injury, death, or substantial
property damage.

Multiple vent/air terminations

1. When terminating multiple Knight wall mount boilers

terminate each vent/air connection as described in this
manual (FIG. 4-5A).

2. Place wall penetrations to obtain minimum clearance of 12

inches between edge of air inlet and adjacent vent outlet,
as shown in FIG. 4-5A for U.S. installations. For Canadian
installations, provide clearances required by CSA B149.1
Installation Code.

3. The air inlet of a Knight wall mount boiler is part of a direct

vent connection. It is not classified as a forced air intake
with regard to spacing from adjacent boiler vents.

ƽ WARNING

12" MIN. BETWEEN EDGE OF AIR

INLET AND ADJACENT VENT OUTLET

VENT / AIR

TERMINATION

VENT

AIR

Figure 4-5A Multiple Vent Terminations (must also
comply with Figure 4-1A)

4

Sidewall direct venting

(continued)

25

Installation & Operation Manual

Figure 4-5B Alternate Multiple Vent Terminations w/Field
Supplied Fittings (must also comply with Figure 4-1B)