beautypg.com

B-30, B-27, Type 24—edwards synchronous wired clocks, type e1 – Lathem Dukane 24A715 User Manual

Page 72

background image

TYPE 24—Edwards Synchronous Wired Clocks, Type E1

During normal operation, 120Vac is applied between the run motor and common lines to
operate the clocks until the 58th minute. At HH:58:00 of each hour, the 120Vac is re-
placed by 120Vdc between the correction and common lines for a period of 200ms, with
the common line being positive. This pulse initiates hourly corrections for clocks that are
less than 60 minutes slow. At 5:58:09 AM and PM, an additional 120Vdc, 200ms pulse is
transmitted to correct clocks that are 60 or more minutes slow.

B-30

24A715/24A715M Master Clock Installation Manual

1

2

3

4

5

6

7

8

CLK1 OR CLK2

x

x

x

x

RELAY

K6 (K8)

RELAY

K5 (K7)

I

I

MASTER CLOCK

FIELD CONNECTIONS

X = Normally open contact

I = Normally closed contact

10 ASB MAX.

120Vac

2

2 = Diode bridge, 200V min PIV,

avg current = # clocks x 0.115A

1 = V250LA4 MOV or equal

1

AC RTN

BLK

RUN MOTOR

+

WHT

COMMON

1

RED

CORRECTION

Figure B-27

Edwards Synchronous Wired Clocks, Type E1

This manual is related to the following products: