B-17, B-15, Type 13—two-wire pulse alternating (24vdc) – Lathem Dukane 24A715 User Manual

Page 59

background image

TYPE 13—Two-Wire Pulse Alternating (24Vdc)

Every minute from 59 seconds to 00 seconds, a 24Vdc signal is applied on lines A and B,
causing the clocks to advance one minute. The polarity of the pulse is alternated each
minute to cause A to be positive with respect to B one minute, then B positive with re-
spect to A the next minute, and so on.

During power interruptions, the master clock accumulates the number of minutes lost.
When power is restored, the master clock sends 30 pulses per minute to correct the
clocks. The clocks can be manually advanced 60 minutes using the master clock. A total
of 62 pulses are issued during manual advance (two normal pulses plus 60 extra advance
pulses).

24A715/24A715M Master Clock Installation Manual

B-17

1

2

3

4

5

6

7

8

CLK1 OR CLK2

x

x

x

x

RELAY

K6 (K8)

RELAY

K5 (K7)

I

I

MASTER CLOCK

FIELD CONNECTIONS

X = Normally open contact

I = Normally closed contact

10 ASB MAX.

+

A

B

1 = V250LA4 MOV or equal

1

2 = 1N4004 diode or equal

2

24Vdc

CLOCKS

Figure B-15

Two-Wire Pulse Alternating (24Vdc)