B-24, B-21, Type 18—national synchronous wired – Lathem Dukane 24A715 User Manual
Page 66
TYPE 18—National Synchronous Wired
For a list of Type 18 clocks, see the chart on the first page of this appendix.
Relay K5 is normally operated to power the clock run motors. Each hour from HH:00:00
to HH:00:28, relay K6 is operated to power the clock correction coils for 28 seconds and
cause hourly corrections. Every 12 hours, from 6:00:00 to 6:27:27, relay K6 is again op-
erated to power the clock correction coils for 27 minutes, causing 12-hour correction.
Manual clock corrections can be issued from the master during any even-numbered
minute except 00.
B-24
24A715/24A715M Master Clock Installation Manual
1
2
3
4
5
6
7
8
CLK1 OR CLK2
x
x
x
x
RELAY
K6 (K8)
RELAY
K5 (K7)
I
I
MASTER CLOCK
FIELD CONNECTIONS
X = Normally open contact
I = Normally closed contact
SOURCE
POWER
10 ASB MAX.
CORRECTION COIL
RUN MOTOR
RETURN
1 = V250LA4 MOV or equal
1
1
1
Figure B-21
National Synchronous Wired