Notes: 1. SFP transceivers are hot-swappable. The switch does not need

to be powered off before installing or removing a transceiver.
However, always first disconnect the network cable before
removing a transceiver.

2. SFP transceivers are not provided in the switch package.

Grounding the Chassis

Before powering on the switch, ground the switch to earth as described
below.

1. Ensure that the rack on which the switch is to be mounted is properly

grounded and in compliance with ETSI ETS 300 253.

2. Ensure that there is a good electrical connection to the grounding

point on the rack (no paint or isolating surface treatment).

3. Disconnect all power cables to the switch.

4. The switch chassis is connected internaly to 0 V. This circuit is

connected to the single-hole grounding terminal on the back of the
switch. The surface area around this terminal is not painted in order to
provide for a good connection. Attach a 6 AWG stranded copper wire
to the grounding terminal on the switch.

5. Then attach the grounding wire to the ground point on the rack.

Caution: The earth connection must not be removed unless all supply

connections have been disconnected.