Parameter assignment and operation of the device

8-7

©

Siemens AG 2010 All Rights Reserved

SICLOCK

®

TC100 Operating Instructions

In this way, you can add your own values to the list of options, and assign
any IP addresses:

For this purpose, you need a notebook or PC with an Ethernet connection to the
device. The notebook must already be in the desired IP subnet.

1. Open a CMD shell on the notebook.

2. Press the button until the list of options is displayed (operating level 2, IP

address flashes, only in this status can new values be added).

3. Now trigger a ping on the notebook with at least 4 attempts to the desired IP

address (e.g. ping –n 5 192.168.1.43).

4. The ping is not answered by the device, but the destination address is added

to the list of options, and can be accepted by a long button press.

8.2.3

Readout versions

The relevant software versions can be readout by one-button operation:

Figure 8-10 Readout versions

The following versions can be readout:

Firmware version TC100

Core version TC400

Core version U300

Processor version

VKRUW

/HYHO

VKRUW

Version ->

VKRUW

V

VKRUW

IP address ->

Mo, 4. Oct. 2010

11:46:48 ->GPS1

Firmware 1.53467

192.168.001.010 -->