Siemens BACnet Heat Pump Controller - Multi-Stage Owner’s Manual
26
Siemens Building Technologies, Inc.
Description Address Application
Description
SWITCH DBAND
90
2583, 2584
Temperature range in degrees that is compared to the
difference between CTL TEMP and CTL STPT. The
difference must exceed this value for temperature control
mode to change over. Changeover is also subject to the
active temperature control loop output being below SWITCH
LIMIT and SWITCH TIME being expired.
NGT MA CTL
{91}
2583, 2584
YES indicates that mixed air control should occur during
night mode. NO indicates that mixed air control will not
occur during night mode.
Valid input: YES or NO.
CTL STPT
{92}
2583, 2584
Actual setpoint value being used as input for the active
temperature control loop.
MA STPT
{93}
2583, 2584
Setpoint of the mixed air control loop.
EHEAT 2 ON
94
2583
Value, in percent, that the heating loopout must exceed for
the second stage of electric heat to turn ON.
EHEAT 3 ON
95
2583
Value, in percent, that the heating loopout must exceed for
the third stage of electric heat to turn ON.
CAL TIMER
96
2583, 2584, 2590
Time interval, in hours, between the calibration sequence.
AOV 3
{97}
2583, 2584, 2590
Analog output 3 controls a 0 to 10V signal.
LOOP TIME
98
2583, 2584
Time, in seconds, between control loop calculations.
ERROR STATUS
{99}
2583, 2584, 2590
Status code indicating any errors detected during controller
power up. A status of 0 indicates there are no problems.
CLG D GAIN
102
2583, 2584
Derivative gain value for the cooling temperature control
loop.
CLG BIAS
103
2583, 2584
Biasing of the cooling temperature control loop.
See CLG LOOPOUT.
HTG D GAIN
104
2583, 2584
Derivative gain value for the heating temperature control
loop.
HTG BIAS
105
2583, 2584
Biasing of the heating temperature control loop.
See HTG LOOPOUT.
1.
Points not listed are not used in this application.
2.
Point numbers that appear in brackets { } may be unbundled at the field panel.