Point Database

Siemens Building Technologies, Inc.

19

Description Address Application

Description

RM STPT MlN

11

2583, 2584

Minimum temperature setpoint in degrees that the controller
can use from the setpoint dial. This overrides any
temperature setpoint from the setpoint dial that falls below
this minimum.
Valid entry range: 48° to 95°F (9° to 35°C)

RM STPT MAX

12

2583, 2584

Maximum temperature setpoint in degrees that the controller
can use from the setpoint dial. This overrides any
temperature setpoint from the setpoint dial that raises above
this maximum.
Valid entry range: 48° to 95°F (9° to 35°C)

RM STPT DIAL

{13}

2583, 2584, 2590

Temperature setpoint in degrees from the room temperature
sensor (not available on all temperature sensor models).
This setpoint will be used for control in day mode (heating or
cooling) when enabled by STPT DIAL (Point 14).
Valid entry range: 48° to 95°F (9° to 35°C)

STPT DIAL

14

2583, 2584

YES indicates that there is a room setpoint dial on the room
temperature sensor and must be used as the temperature
setpoint for control in day/occupied mode. NO indicates that
the appropriate preset setpoint will be used as the
temperature setpoint for control in day/occupied heating or
cooling mode.
Valid input: YES or NO

AUX TEMP

{15}

2590

Actual reading from a 10K Ω thermistor connected to the
controller's AI 5 input. When a thermistor is connected at
Al 5, DI 5 is not available. See DI 5. The physical input can
not be used for both analog and digital input at the same
time.

MA TEMP

{15}

2583, 2584

Actual reading from a 10K Ω thermistor connected to the
controller's Al 5 input. When a thermistor is connected at
Al 5, DI 5 is not available. See DI 5. The physical input can
not be used for both analog and digital input at the same
time.

CMP2 ON

16

2583

Value, in percent, that the active temperature control loop
output must exceed for compressor 2 to turn ON. Actual
turn on is subject to the CMP2 MlN OFF time being expired.

HTG CMP2 ON

16

2584

Value, in percent, that the heating control loop output must
exceed for compressor 2 to turn ON. Actual turn on is
subject to the CMP2 MlN OFF time being expired.

CMP2 OFF

17

2583

Value, in percent, that the active temperature control loop
output must go below for compressor 2 to turn OFF. Actual
turn off is subject to the CMP2 MlN ON time being expired.

HTG CMP2 OFF

17

2584

Value, in percent, that the heating control loop output must
go below for compressor 2 to turn OFF. Actual turn off is
subject to the CMP2 MlN ON time being expired.

WALL SWITCH

18

2583, 2584, 2590

YES indicates that the controller is to monitor the status of a
wall switch that is connected to Dl 2. NO indicates that the
controller will not monitor the status of a wall switch, even if
one is connected.
Valid input: YES or NO