Point Database
Siemens Building Technologies, Inc.
21
Description Address Application
Description
DAY.NGT
{29}
2583, 2584, 2590
Indicates the mode in which the controller is operating.
Day temperature setpoints are used in day mode.
Night temperature setpoints are used in night mode. This
point is normally set by the field panel.
CLG CMP1 ON
30
2584
Value, in percent, that the cooling temperature control loop
output must exceed for cooling compressor 1 to turn ON.
Actual turn on is subject to the CLG1 MlN OFF time being
expired.
CLG CMP1 OFF
31
2584
Value, in percent, that the cooling temperature control loop
output must go below for cooling compressor 1 to turn OFF.
Actual turn off is subject to the CLG1 MlN ON time being
expired.
CLG1 MlN OFF
32
2584
Minimum time, in minutes, that cooling compressor 1 will
remain OFF before turning ON.
CLG1 MlN ON
33
2584
Minimum time, in minutes, that cooling compressor 1 will
remain ON before turning OFF.
CLG CMP2 ON
34
2584
Value, in percent, that the cooling temperature control loop
output must exceed for cooling compressor 2 to turn ON.
Actual turn on is subject to the CLG 2 MIN OFF time being
expired.
CMP3 ON
34
2583
Value, in percent, that the active temperature control loop
output must exceed for compressor 3 to turn ON. Actual
turn on is subject to the CMP3 MlN OFF time being expired.
CLG CMP2 OFF
35
2584
Value, in percent, that the cooling temperature control loop
output must exceed for cooling compressor 2 to turn OFF.
Actual turn off is subject to the CLG2 MIN ON time being
expired.
CMP3 OFF
35
2583
Value, in percent, that the active temperature control loop
output must go below for compressor 3 to turn OFF. Actual
turn off is subject to the CMP3 MlN ON time being expired.
CLG2 MIN OFF
36
2584
Minimum time, in minutes, that cooling compressor 2 will
remain OFF before turning ON.
CMP3 MlN OFF
36
2583
Minimum time, in minutes, that compressor 3 will remain
OFF before turning ON.
CLG2 MlN ON
37
2584
Minimum time, in minutes, that cooling compressor 2 will
remain ON before turning OFF.
CMP3 MlN ON
37
2583
Minimum time, in minutes, that compressor 3 will remain ON
before turning OFF.
DAMPER TYPE
38
2583, 2584
FLOAT indicates that a floating control damper is used.
SPRING indicates that a spring return damper is used.
Valid input: FLOAT or SPRING.
AO DIR.REV
39
2583, 2584
Configuration setup code for AO. Allows the AO to be direct
(normally closed) or reverse acting (normally open).
AOV1
{40}
2583, 2584, 2590
Analog output 1 controls a 0 to 10V signal.