beautypg.com

Siemens BACNET 125-699 User Manual

Page 29

background image

Point Database

Siemens Building Technologies, Inc.

21

Description Address Application

Description

DAY.NGT

{29}

2583, 2584, 2590

Indicates the mode in which the controller is operating.
Day temperature setpoints are used in day mode.
Night temperature setpoints are used in night mode. This
point is normally set by the field panel.

CLG CMP1 ON

30

2584

Value, in percent, that the cooling temperature control loop
output must exceed for cooling compressor 1 to turn ON.
Actual turn on is subject to the CLG1 MlN OFF time being
expired.

CLG CMP1 OFF

31

2584

Value, in percent, that the cooling temperature control loop
output must go below for cooling compressor 1 to turn OFF.
Actual turn off is subject to the CLG1 MlN ON time being
expired.

CLG1 MlN OFF

32

2584

Minimum time, in minutes, that cooling compressor 1 will
remain OFF before turning ON.

CLG1 MlN ON

33

2584

Minimum time, in minutes, that cooling compressor 1 will
remain ON before turning OFF.

CLG CMP2 ON

34

2584

Value, in percent, that the cooling temperature control loop
output must exceed for cooling compressor 2 to turn ON.
Actual turn on is subject to the CLG 2 MIN OFF time being
expired.

CMP3 ON

34

2583

Value, in percent, that the active temperature control loop
output must exceed for compressor 3 to turn ON. Actual
turn on is subject to the CMP3 MlN OFF time being expired.

CLG CMP2 OFF

35

2584

Value, in percent, that the cooling temperature control loop
output must exceed for cooling compressor 2 to turn OFF.
Actual turn off is subject to the CLG2 MIN ON time being
expired.

CMP3 OFF

35

2583

Value, in percent, that the active temperature control loop
output must go below for compressor 3 to turn OFF. Actual
turn off is subject to the CMP3 MlN ON time being expired.

CLG2 MIN OFF

36

2584

Minimum time, in minutes, that cooling compressor 2 will
remain OFF before turning ON.

CMP3 MlN OFF

36

2583

Minimum time, in minutes, that compressor 3 will remain
OFF before turning ON.

CLG2 MlN ON

37

2584

Minimum time, in minutes, that cooling compressor 2 will
remain ON before turning OFF.

CMP3 MlN ON

37

2583

Minimum time, in minutes, that compressor 3 will remain ON
before turning OFF.

DAMPER TYPE

38

2583, 2584

FLOAT indicates that a floating control damper is used.
SPRING indicates that a spring return damper is used.
Valid input: FLOAT or SPRING.

AO DIR.REV

39

2583, 2584

Configuration setup code for AO. Allows the AO to be direct
(normally closed) or reverse acting (normally open).

AOV1

{40}

2583, 2584, 2590

Analog output 1 controls a 0 to 10V signal.