Siemens BACnet Heat Pump Controller - Multi-Stage Owner’s Manual

24

Siemens Building Technologies, Inc.

Description Address Application

Description

CYCLE FAN

60

2583, 2584

YES indicates that the fan should cycle ON and OFF with
the compressor during day mode. NO indicates that the fan
should remain ON constantly in day mode.
Valid input: YES or NO

NOTE:

In either case, the fan will cycle during night mode.

FREE CLG ON

61

2583, 2584

Value, in percent, that the cooling loopout must exceed for
free cooling to turn ON.

FREE CLG OFF

62

2583, 2584

Value, in percent, that the cooling loopout must exceed for
free cooling to turn OFF.

CLG P GAIN

63

2583, 2584

Proportional gain value for the cooling temperature control
loop.

CLG I GAIN

64

2583, 2584

Integral gain value for the cooling temperature control loop.

STPT SPAN

65

2583, 2584

Used to configure the allowable temperature range when
using the optional Relative Setpoint Adjustment feature.

STAT TYPE

66

2583, 2584

Default = NORMAL. Can be set to OFFSET for optional
Relative Setpoint Adjustment feature when room sensor part
number SB1-0916 or SB1-1072 is used.
Valid input: NORMAL or OFFSET

HTG P GAIN

67

2583, 2584

Proportional gain value for the heating temperature control
loop.

HTG I GAIN

68

2583, 2584

Integral gain value for the heating temperature control loop.

HP DO OVRD

69

2583, 2584

For the commanding of critical digital outputs. CAUTION:
IMPROPER USE CAN CAUSE PERMANENT EQUIPMENT
DAMAGE.

STPT OFFSET

{70}

2583, 2584

For use with optional Relative Setpoint Adjustment feature.

MA P GAIN

{71}

2583, 2584

Proportional gain value for the mixed air control loop.

MA I GAIN

{72}

2583, 2584

Integral gain value for the mixed air control loop.

MA D GAIN

{73}

2583, 2584

Derivative gain value for the mixed air control loop.

MA BIAS

{74}

2583, 2584

Biasing of the mixed air control loop.

CMP TOTL

75

2583

Number of compressors used by the application.
Valid values: 0, 1, 2, 3

HTG CMP TOTL

75

2584

Number of heating compressors used by the application.
Valid values: 0, 1, 2

EHTG STG CNT

76

2583, 2584

Number of electric heating stages used by the application.
Valid values: 0, 1, 2, 3

CLG CMP TOTL

77

2584

Number of cooling compressors used by the application.
Valid values: 0, 1, 2

CTL TEMP

{78}

2583, 2584, 2590

Temperature used as input for the temperature
control loops. This value will be the same as the value in
ROOM TEMP + RMTMP OFFSET unless it is overridden.

CLG LOOPOUT

{79}

2583, 2584

Cooling temperature control loop output value in percent.