Siemens BACNET 125-699 User Manual
Page 32
Siemens BACnet Heat Pump Controller - Multi-Stage Owner’s Manual
24
Siemens Building Technologies, Inc.
Description Address Application
Description
CYCLE FAN
60
2583, 2584
YES indicates that the fan should cycle ON and OFF with
the compressor during day mode. NO indicates that the fan
should remain ON constantly in day mode.
Valid input: YES or NO
NOTE:
In either case, the fan will cycle during night mode.
FREE CLG ON
61
2583, 2584
Value, in percent, that the cooling loopout must exceed for
free cooling to turn ON.
FREE CLG OFF
62
2583, 2584
Value, in percent, that the cooling loopout must exceed for
free cooling to turn OFF.
CLG P GAIN
63
2583, 2584
Proportional gain value for the cooling temperature control
loop.
CLG I GAIN
64
2583, 2584
Integral gain value for the cooling temperature control loop.
STPT SPAN
65
2583, 2584
Used to configure the allowable temperature range when
using the optional Relative Setpoint Adjustment feature.
STAT TYPE
66
2583, 2584
Default = NORMAL. Can be set to OFFSET for optional
Relative Setpoint Adjustment feature when room sensor part
number SB1-0916 or SB1-1072 is used.
Valid input: NORMAL or OFFSET
HTG P GAIN
67
2583, 2584
Proportional gain value for the heating temperature control
loop.
HTG I GAIN
68
2583, 2584
Integral gain value for the heating temperature control loop.
HP DO OVRD
69
2583, 2584
For the commanding of critical digital outputs. CAUTION:
IMPROPER USE CAN CAUSE PERMANENT EQUIPMENT
DAMAGE.
STPT OFFSET
{70}
2583, 2584
For use with optional Relative Setpoint Adjustment feature.
MA P GAIN
{71}
2583, 2584
Proportional gain value for the mixed air control loop.
MA I GAIN
{72}
2583, 2584
Integral gain value for the mixed air control loop.
MA D GAIN
{73}
2583, 2584
Derivative gain value for the mixed air control loop.
MA BIAS
{74}
2583, 2584
Biasing of the mixed air control loop.
CMP TOTL
75
2583
Number of compressors used by the application.
Valid values: 0, 1, 2, 3
HTG CMP TOTL
75
2584
Number of heating compressors used by the application.
Valid values: 0, 1, 2
EHTG STG CNT
76
2583, 2584
Number of electric heating stages used by the application.
Valid values: 0, 1, 2, 3
CLG CMP TOTL
77
2584
Number of cooling compressors used by the application.
Valid values: 0, 1, 2
CTL TEMP
{78}
2583, 2584, 2590
Temperature used as input for the temperature
control loops. This value will be the same as the value in
ROOM TEMP + RMTMP OFFSET unless it is overridden.
CLG LOOPOUT
{79}
2583, 2584
Cooling temperature control loop output value in percent.