Point database, Overview – Siemens BACNET 125-699 User Manual
Page 26
Siemens Building Technologies, Inc.
18
3
Point Database
Overview
This chapter presents a description of the Siemens BACnet Heat Pump Controller—Multi-
Stage point database including point descriptors, point addresses, and a listing of
applications in which each point is found.
Description Address Application
Description
CTLR ADDRESS
01
2583, 2584, 2590
ldentifies the controller on the FLN trunk.
APPLICATION
02
2583, 2584, 2590
Identification number of the program running in the
controller.
Valid input: 2583, 2584, 2590
RETURN DELAY
03
2583, 2584
Amount of time the heat pump will remain off after a return
from power failure.
ROOM TEMP
{04}
2583, 2584, 2590
Actual reading from the room temperature sensor.
HEAT.COOL
{05}
2583, 2584
Current mode of operation for applications that can be either
a heating mode or a cooling mode.
DAY CLG STPT
06
2583, 2584
Temperature setpoint in degrees that the controller
maintains during day periods in cooling mode if a room
temperature sensor setpoint dial is not present or is not
used. See STPT DIAL.
Valid entry range: 48° to 95°F (9°to 35°C)
DAY HTG STPT
07
2583, 2584
Temperature setpoint in degrees that the controller
maintains during day periods in heating mode if a room
temperature sensor setpoint dial is not present or is not
used. See STPT DIAL.
Valid entry range: 48° to 95°F (9° to 35°C)
NGT CLG STPT
08
2583, 2584
Temperature setpoint in degrees that the controller
maintains during night periods in cooling mode.
Valid entry range: 48° to 95°F (9° to 35°C)
NGT HTG STPT
09
2583, 2584
Temperature setpoint in degrees that the controller
maintains during night periods in heating mode.
Valid entry range: 48° to 95°F (9° to 35°C)
DMPR MlN POS
10
2583, 2584
Minimum position the damper will be commanded to during
day mode.