Mechanical design, General, Dimensions – Siemens RDG400 User Manual
Page 39
39 / 42
Siemens
RDG100, RDG100T, RDG110, RDG140, RDG160 Basic Documentation
CE1P3182en
Building Technologies
Technical data
28 May 2009
Operation
Climatic conditions
Temperature
Humidity
As per IEC 721-3-3
Class 3K5
0...50 °C
<95% r.h.
Transport
Climatic conditions
Temperature
Humidity
Mechanical conditions
As per IEC 721-3-2
Class 2K3
−25... 60 °C
<95% r.h.
Class 2M2
Storage
Climatic conditions
Temperature
Humidity
As per IEC 721-3-1
Class 1K3
−25... 60 °C
<95% r.h.
conformity
EMC directive
2004/108/EC
N474
C-tick conformity to
EMC emission standard
AS/NSZ 4251.1:1999
Reduction of hazardous substances
2002/95/EC
Product standards
Automatic electrical controls for household and
similar use
Special requirements for temperature-dependent
controls
Electronic control type
As per EN 60730–1
As per EN 60730–2-9
2.B (micro-disconnection on
operation)
Electromagnetic compatibility
Emissions
Immunity
As per IEC/EN 61000-6-3
As per IEC/EN 61000-6-2
Safety class
III as per EN 60730
Pollution class
Normal
Degree of protection of housing
IP30 as per EN 60529
Connection terminals
Solid wires or prepared
stranded wires
1 x 0.4…2.5 mm
2
or 2 x 0.4…1.5 mm
2
Housing front color
RAL 9003 white
Weight 0.350
kg
Environmental
conditions
Standards
General