Siemens RDG400 User Manual
Page 18
18 / 42
Siemens
RDG100…/RDG110…/RDG140.../RDG160… Basic Documentation
CE1P3182en
Building Technologies
Functions
28 May 2009
4.7.3
Control outputs overview
(setting via DIP 4 / 5 and parameters P46 / P47)
Control outputs
Application
ON/
O
FF
(2-position)
Modulating
PWM
(2-position)
Modulating
3-position
Modulating
DC 0 … 10
V
Single duct
Single duct and electrical heater
Single duct and radiator / floor heating
Single-duct heating / cooling coil
The function of the control outputs is set via DIP switches 4 and 5:
ON
OFF
1
2
3
4
5
ON
OFF
1
2
3
4
5
ON
OFF
1
2
3
4
5
ON
OFF
1
2
3
4
5
3181
D101
DIP 4: Y10 =
0 … 10 V
0 … 10 V
10 … 0 V inverted 10 … 0 V inv
DIP 5: Y1 / Y2 =
2-position
3-position
2-position
3-position
Y1, Y2:
If 2-position is selected, the factory setting is on/off.
If you want PWM (pulse width modulation), set parameter P46 to 2 = PWM.
P47:
• 0 = VAV box DC 0 … 10 V control signal
• 1 = VAV box : 3-position control signal
For details concerning connection of peripheral devices and setting of the DIP
switches please refer to the mounting instructions, M3182 [3]:
Note