RDG100…/RDG110…/RDG140.../RDG160… Basic Documentation

CE1P3182en

Building Technologies

Functions

28 May 2009

4.7.3

Control outputs overview
(setting via DIP 4 / 5 and parameters P46 / P47)

Control outputs




Application

ON/

O

FF

(2-position)

Modulating

PWM

(2-position)

Modulating

3-position

Modulating

DC 0 … 10

V

Single duct

Single duct and electrical heater

Single duct and radiator / floor heating

Single-duct heating / cooling coil


The function of the control outputs is set via DIP switches 4 and 5:

ON

OFF

1

2

3

4

5

ON

OFF

1

2

3

4

5

ON

OFF

1

2

3

4

5

ON

OFF

1

2

3

4

5

3181

D101

DIP 4: Y10 =

0 … 10 V

0 … 10 V

10 … 0 V inverted 10 … 0 V inv

DIP 5: Y1 / Y2 =

2-position

3-position

2-position

3-position


Y1, Y2:
If 2-position is selected, the factory setting is on/off.
If you want PWM (pulse width modulation), set parameter P46 to 2 = PWM.

P47:
• 0 = VAV box DC 0 … 10 V control signal
• 1 = VAV box : 3-position control signal

For details concerning connection of peripheral devices and setting of the DIP
switches please refer to the mounting instructions, M3182 [3]:

Note