Functions

28 May 2009

If the button lock function is enabled by parameter P14, then the buttons will be
locked or unlocked by pressing the right button for 3 sec.
If “Auto lock” is configured, then the thermostat will automatically lock the buttons
10 sec after the last adjustment.


The thermostat can be forced into Energy Saving mode, e.g. when a window is
opened. The window contact can be connected to digital input D1 (or
multifunctional input X1, X2). Set parameter P42 (P38, P40) to 3.

The left button switches the operating mode from Energy Saving to Comfort for the
period preset in P68, if the following conditions are fulfilled:
• The operating mode switchover contact is closed (connected to input X1, X2,

D1, parameter P38, P40, P42 set to 3)

• Parameter P68 (extend Comfort period) is greater than 0


During the temporary Comfort mode extension, timer symbol appears.

If parameter P68 (extend Comfort period) = 0, extended Comfort cannot be
activated; pressing the left button will show “OFF” (blinking 3 times)

The current operating mode can be forced temporarily into Comfort or Energy
Saving / Protection mode. The time period is adjusted via the rotary knob:
• Extend presence: Set the device to Comfort mode for the selected time period
• Extend absence: Set the device to Energy Saving / Protection mode for the

selected time period


To activate the function, keep the left button pressed and, within 3 seconds, turn
the rotary knob
• clockwise for extended presence
• counterclockwise for extended absence
The rotary knob adjusts the time period:
• Extend presence: 0.00…+9:30 in steps of 30 minutes; symbol appears
• Extend absence: 0.00…–9:30 in steps of 30 minutes; symbol or appears

During the extended presence / absence period, timer symbol appears.

Function

User operating mode
selection

Operating
mode when
activating
function

Function

Operating mode
during function

Operating mode at
the end of function

Comf Extension

Comf

Prot

Comf Absence

Prot

Comf

Prot Not

available

-

-

Comf Extension

Comf

Eco

Comf Absence

Eco

Comf

Eco Extension

Comf

Eco

Eco Absence

Eco

Comf

Prot Not

available

-

-


Button lock

Operating mode
switchover contact
(Window contact)

Extended Comfort
mode
(operating mode
switchover contact
closed)

Temporary timer for
extension of presence /
absence