Parameters service level – Siemens RDG400 User Manual
Page 31
31 / 42
Siemens
RDG100, RDG100T, RDG110, RDG140, RDG160 Basic Documentation
CE1P3182en
Building Technologies
Functions
28 May 2009
Param
et
er
Name
Factory setting
Range
RDG400
Diagnostics & test
d01
Application type
Diagnostics
0:= --- (No application)
1:= Single-duct
2:= Single-duct with el. heater
3:= Single-duct with radiator
4:= Single-duct with h/c coil
d02
X1 status
Diagnostics
0 = Not activated (for DI)
1 = activated (DI)
0…49 °C = cur. temp. value (for AI)
00 = HC input short
100 = HC input open
d03
X2 status
Diagnostics
0 = Not activated (for DI)
1 = activated (DI)
0…49 °C = cur. temp. value (for AI)
00 = HC input short
100 = HC input open
d04
D1 status
Diagnostics
0 = Not activated (for DI)
1 = activated (DI)
00 = HC input short
100 = HC input open
d05
Test mode for checking the Y1/Y2
actuator direction
(press left button to escape)
---
“---“ = no signal on outputs Y1 and Y2
OPE = output Y1 forced open
CLO = output Y2 forced closing